Permit Information
Permit NumberFIR05-00881
StatusVoid/No Violation
Name TREASURE VALLEY FIRE PROTECTION
Site Address 2291 N 15TH ST
Project NameSPR VILLA HIGHLANDS
Customer Number 
ePlanReview 
Description
VILLA HIGHLANDS * To install complete overhead NFPA 13 fire sprinkler protection system construct a new 63,830-ft/2, three story, independent living facility with 50 dwelling units, a common kitchen, dining room and multi-purpose area on the first floor for the residence use only. There is a 500-ft/2 arts and craft room located on the third floor, a 300-ft/2 exercise room and a 200-ft/2 projection room on the second floor. The first floor is 22,758-ft/2, the second floor is 19,978-ft/2 and the third floor is 20,093-ft/2. NOTE: This structure is fully fire sprinklered per NFPA 13 for area increase. The fire protection work shall be in accordance with minimum requirements of IFC-2003, and attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this permit, to provide witness of compliance verification of meeting minimum code. The underground fire service supply main was permitted by the same company under FIR05-00600. This permit is attached to BLD05-00087.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/11/20095/11/20095/11/2009PDONE
DetailsForrest France
Discussion with contractor regarding permit status and process for void or expiration.
Permit VOIDED5/11/20095/11/20095/11/2009 DONE
DetailsAlexandra L. DeYoung
Per Forrest- building burnt down, permit can't be finaled
INSP-Sprinkler Rough-in5/2/20065/3/20065/3/2006PPART
DetailsForrest France
Partial inspection for the 1st floor SW side overhead piping rough-in, need to provide vertical restraint for heads at arm-overs with ATR/ring hangers, provide protection below stairs, watch surface mounted obstructions that may develop due to close proximity of pendent heads and junction boxes at some locations, no plumbing pipe is allowed to be supported by fire sprinkler pipe.
Sprinkler Plan Check4/3/2006 4/26/2006 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  4/26/2006 DONE
Telephone call  4/26/2006 DONE
tlk to brodie stenquist ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  4/26/2006 DONE
Issue and Print Permit  4/26/2006 DONE
Plan assigned to (Bill)3/14/2006 4/26/2006 DONE
Plan resubmittals received  4/3/2006  
Inspection Record Card- Fire3/29/2006 3/29/2006 DONE
Permit Ready to Issue  3/29/2006 DONE
Telephone call  3/29/2006 DONE
left mess that permit is ready
Issue and Print Permit  3/29/2006 DONE
Sprinkler Plan Check3/13/2006 3/28/2006 PART
1. Residential design is flawed. This is a building which requires full NFPA 13 installation protection, per Special Design Areas, "11.2.3.5 Residential Sprinklers."
Plan resubmittals received  3/13/2006  
Sprinkler Plan Check2/10/2006 3/1/2006 PART
DetailsBill Alexander
The data has been moved to a Word document attached to this case.
PLANS/APPL TAKEN TO FRONT DESK  3/1/2006 DONE
Permit Ready to Issue  3/1/2006  
Inspection Record Card- Fire3/1/2006 3/1/2006 DONE
Telephone call  3/1/2006  
Informed Crystal (Treasure Valley Fire Protection) ###-#### to pick up permit 3-1-06 eus
Issue and Print Permit  3/1/2006 DONE
Plan assigned to (Bill)12/20/2005 3/1/2006 DONE
Plan resubmittals received  2/10/2006 DONE
Miscellaneous action  1/12/2006 DONE
Took failed documents to permit desk for returning.
Meeting  1/12/2006 DONE
Met with Ron Stenquist & George Edes, concerning plans 11:30am and Ron aggreed they had problems.
Miscellaneous action  1/11/2006 DONE
Requested the desinger to submit a single set of plans in clarifty and scale that can be interpreted in meeting code without the use of a magnifying device.
Sprinkler Plan Check12/20/2005 1/11/2006 FAIL
Provide more plan clarity and larger scale.
Provide more ceiling details through FP-2 and any other qustionable area in relation to heads and there location, listing, etc., Room identifications, Closets identified and the exception allowed, Bathroom square footage, construction information for potty, showers and wash areas seperation if not sprinklering,
Show the (required) elevations of lines and mains, etc., (reference 14.1.3[37]),
Standpipe hose stations locations (on intermediate landings),
All piping types identified and where being installed, whether installing fire sprinkler protection in the Gravity Chute or not in this facility, the required fire sprinklers protection shall be connected and supervised by this building system, which must be connected on these plans and addressed in this permit. (NFPA 13-13.15.2.1.1)
"Express" drain sized and where it goes, etc., etc., etc. per BMC 7-01-50 IFC 901.2, 105.4.2.
Case Summary  12/20/2005  
Application received  12/20/2005