INSP-Final Inspection | 5/11/2009 | 5/11/2009 | 5/11/2009 | P | DONE |
Forrest France
|
|
|
Discussion with contractor regarding permit status and process for void or expiration.
|
Permit VOIDED | 5/11/2009 | 5/11/2009 | 5/11/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
Per Forrest- building burnt down, permit can't be finaled
|
INSP-Sprinkler Rough-in | 5/2/2006 | 5/3/2006 | 5/3/2006 | P | PART |
Forrest France
|
|
|
Partial inspection for the 1st floor SW side overhead piping rough-in, need to provide vertical restraint for heads at arm-overs with ATR/ring hangers, provide protection below stairs, watch surface mounted obstructions that may develop due to close proximity of pendent heads and junction boxes at some locations, no plumbing pipe is allowed to be supported by fire sprinkler pipe.
|
Sprinkler Plan Check | 4/3/2006 | | 4/26/2006 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/26/2006 | | DONE |
|
|
|
|
Telephone call | | | 4/26/2006 | | DONE |
|
|
|
tlk to brodie stenquist ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 4/26/2006 | | DONE |
|
|
|
|
Issue and Print Permit | | | 4/26/2006 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 3/14/2006 | | 4/26/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 4/3/2006 | | |
|
|
|
|
Inspection Record Card- Fire | 3/29/2006 | | 3/29/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/29/2006 | | DONE |
|
|
|
|
Telephone call | | | 3/29/2006 | | DONE |
|
|
|
left mess that permit is ready
|
Issue and Print Permit | | | 3/29/2006 | | DONE |
|
|
|
|
Sprinkler Plan Check | 3/13/2006 | | 3/28/2006 | | PART |
|
|
|
1. Residential design is flawed. This is a building which requires full NFPA 13 installation protection, per Special Design Areas, "11.2.3.5 Residential Sprinklers."
|
Plan resubmittals received | | | 3/13/2006 | | |
|
|
|
|
Sprinkler Plan Check | 2/10/2006 | | 3/1/2006 | | PART |
Bill Alexander
|
|
|
The data has been moved to a Word document attached to this case.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/1/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/1/2006 | | |
|
|
|
|
Inspection Record Card- Fire | 3/1/2006 | | 3/1/2006 | | DONE |
|
|
|
|
Telephone call | | | 3/1/2006 | | |
|
|
|
Informed Crystal (Treasure Valley Fire Protection) ###-#### to pick up permit 3-1-06 eus
|
Issue and Print Permit | | | 3/1/2006 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 12/20/2005 | | 3/1/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 2/10/2006 | | DONE |
|
|
|
|
Miscellaneous action | | | 1/12/2006 | | DONE |
|
|
|
Took failed documents to permit desk for returning.
|
Meeting | | | 1/12/2006 | | DONE |
|
|
|
Met with Ron Stenquist & George Edes, concerning plans 11:30am and Ron aggreed they had problems.
|
Miscellaneous action | | | 1/11/2006 | | DONE |
|
|
|
Requested the desinger to submit a single set of plans in clarifty and scale that can be interpreted in meeting code without the use of a magnifying device.
|
Sprinkler Plan Check | 12/20/2005 | | 1/11/2006 | | FAIL |
|
|
|
Provide more plan clarity and larger scale.
Provide more ceiling details through FP-2 and any other qustionable area in relation to heads and there location, listing, etc., Room identifications, Closets identified and the exception allowed, Bathroom square footage, construction information for potty, showers and wash areas seperation if not sprinklering,
Show the (required) elevations of lines and mains, etc., (reference 14.1.3[37]),
Standpipe hose stations locations (on intermediate landings),
All piping types identified and where being installed, whether installing fire sprinkler protection in the Gravity Chute or not in this facility, the required fire sprinklers protection shall be connected and supervised by this building system, which must be connected on these plans and addressed in this permit. (NFPA 13-13.15.2.1.1)
"Express" drain sized and where it goes, etc., etc., etc. per BMC 7-01-50 IFC 901.2, 105.4.2.
|
Case Summary | | | 12/20/2005 | | |
|
|
|
|
Application received | | | 12/20/2005 | | |
|
|
|
|