Permit Information
Permit NumberFIR05-00884
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 900 N LIBERTY ST
Project Namealm -ST AL'S OFFICE #5-2ND FLR
Customer Number915448303
ePlanReview 
Description
To provide total notification and seven duct detectors for HVAC in the remodeled area on the second floor. The existing required manual fire alarm system includes sprinkler monitoring, HVAC shutdown, elevator recall/shutdown , fire/smoke damper control and notification throughout.

The building permit BLD05-02966 is to finish out a 1st time tenant space of 3,368 sq. ft. for a medical office space. To construct interior non-combustible, non-bearing walls to create new offices, exam rooms, waiting / reception, accessible restrooms and support areas for Perinatology Clinic; install electrical, plumbing, mechanical, sprinkler and alarm system to meet tenant needs and comply with codes; install suspended ceiling grid system per CISCA 0-2 with supported fixtures, interior millwork, door assemblies & finishes. All per approved plans to include red-lined notes on plans and attached plan review conditions of all reviewing agencies. (drs) (PERINATOLOGY CLINIC)(ST AL'S OFFICE MOB BLDG #5-2ND FLR)

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/30/20063/31/20063/31/2006PPASS
DetailsTroy Cobbley
Permit finaled
Plan resubmittals received  3/21/2006  
Issue and Print Permit  2/17/2006 DONE
Alarm Plan Check  2/16/2006 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  2/16/2006 DONE
Inspection Record Card- Fire2/16/2006 2/16/2006 DONE
Permit Ready to Issue  2/16/2006  
Telephone call  2/16/2006 DONE
left mess that permit is ready
Plan resubmittals received  1/31/2006  
Plan assigned to (Mary)12/22/2005 1/11/2006 DONE
Alarm Plan Check  1/11/2006 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  1/11/2006 DONE
Inspection Record Card- Fire1/11/2006 1/11/2006 DONE
Permit Ready to Issue  1/11/2006  
Telephone call  1/11/2006 DONE
tlk to charlie bayne ###-#### that permit and fees are ready to be picked up
Issue and Print Permit  1/11/2006 DONE
Plan resubmittals received  1/9/2006 DONE
Case Summary  1/9/2006 DONE
Alarm Plan Check  1/5/2006 FAIL
Sheet 2 battery calculation requires revision.

Sheet 3 note 8 required revision. Someone will stop and mark up the drawings.
Telephone call  1/5/2006 DONE
Questions to Charlie Bayne regarding the FACP battery calc (states not enough MAPNET cards available) and keyed note #8 on sheet 3, install duct detectors on room side of fresh air intake? Charlie stated he would get back to me.
Application received  12/22/2005  
Case Summary  12/22/2005 DONE