Permit Information
Permit NumberFIR05-00889
StatusFinaled
Name PROTEX
Site Address 733 W BROAD ST
Project NameBODO BLDG #8 - ALM
Customer Number 
ePlanReview 
Description
The shell/core fire alarm permit FIR05-00695 shall be finaled prior to occupancy for this space. To provide total notification in the new TI space (1st floor, 733 W. Broad, BODO #8) and required manual pull stations at two exits. 2/26/2006 - Plan Modification. A fire/smoke damper has been added. A 120VAC smoke detector will be monitored by the FACP. No written comments. Battery calculations appear to be sufficient. Provide updated building map to the PDS Fire Inspector at time of inspection.

The associated building permit (BLD05-02976) is to create a 771 square foot retail sales / candy processing tenant space on the 1st story of an 11 story high-rise building. Egress is directly to the outside at grade. Work is to include interior nonbearing walls, suspended ceilings, a restroom accessible to the disabled, and finishes. The work is required to comply with the approved drawings, the plan review report, and all applicable codes. The fire sprinkler system shall comply with NFPA 13 as regulated by the Fire Department. **CJW** (CARRE CHOCOLATES - BODO BLDG #8 - 1ST STORY) This building is fire sprinklered because it is a high-rise building.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/26/20072/26/20072/26/2007PPASS
DetailsForrest France
TI Fire alarm permit finaled.
INSP-Final Inspection3/20/20063/21/20063/21/2006PPART
DetailsForrest France
Corrections have been made, final pending completion of the related shell alarm permit.
INSP-Final Inspection3/15/20063/17/20063/17/2006AFAIL
DetailsForrest France
Insufficient visual coverage at the "work area" as indicated on plans, duct detector and pull stations tested okay.
CHANGE STATUS TO (ISS)  3/1/2006  
permit picked up and fees paid
(F) Reprint permit  3/1/2006 DONE
Telephone call  2/27/2006 DONE
Requested matrix and battery calculations.
Plan resubmittals received  2/27/2006 DONE
Received matrix and battery calculation.
Inspection Record Card- Fire2/27/2006 2/27/2006 DONE
Permit Ready to Issue  2/27/2006 DONE
Telephone call  2/27/2006 DONE
called ###-#### and told Rob permit is ready and fee
Alarm Plan Check  2/26/2006 PASS
Plan Modification to add smoke detector for fire/smoke damper control. All fire/smoke dampers will be field verified for smoke detector location and functionality.

Approved pending PDS Fire Inspector field verification. No comments written.
PLANS/APPL TAKEN TO FRONT DESK  2/26/2006 DONE
Case Summary  2/24/2006 DONE
Plan resubmittals received  2/24/2006 DONE
Issue and Print Permit  1/11/2006 DONE
Plan assigned to (Mary)12/22/2005 1/10/2006 DONE
Alarm Plan Check  1/10/2006 PASS
Approved pending PDS Fire Inspector field verification. No comments written.
PLANS/APPL TAKEN TO FRONT DESK  1/10/2006  
Permit Ready to Issue  1/10/2006 DONE
Inspection Record Card- Fire1/10/2006 1/10/2006 DONE
Telephone call  1/10/2006 DONE
Spoke with Terie and told her that permit is ready & fees///1/10/06 @2:25pm BAS
Case Summary  1/6/2006 DONE
Plan resubmittals received  1/6/2006 DONE
Alarm Plan Check  1/5/2006 FAIL
No written comments. Per telephone coversation with Rob Ahten.

1) Plan sheet indicates BODO #4, 850 W. Broad St. This TI address is BODO #8, 733 W. Borad St.

2) Insufficient visual coverage in the work area.

3) Manual pull station is more than 5' from the front door.
Application received  12/22/2005  
Case Summary  12/22/2005 DONE