INSP-Final Inspection | 2/26/2007 | 2/26/2007 | 2/26/2007 | P | PASS |
Forrest France
|
|
|
TI Fire alarm permit finaled.
|
INSP-Final Inspection | 3/20/2006 | 3/21/2006 | 3/21/2006 | P | PART |
Forrest France
|
|
|
Corrections have been made, final pending completion of the related shell alarm permit.
|
INSP-Final Inspection | 3/15/2006 | 3/17/2006 | 3/17/2006 | A | FAIL |
Forrest France
|
|
|
Insufficient visual coverage at the "work area" as indicated on plans, duct detector and pull stations tested okay.
|
CHANGE STATUS TO (ISS) | | | 3/1/2006 | | |
|
|
|
permit picked up and fees paid
|
(F) Reprint permit | | | 3/1/2006 | | DONE |
|
|
|
|
Telephone call | | | 2/27/2006 | | DONE |
|
|
|
Requested matrix and battery calculations.
|
Plan resubmittals received | | | 2/27/2006 | | DONE |
|
|
|
Received matrix and battery calculation.
|
Inspection Record Card- Fire | 2/27/2006 | | 2/27/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/27/2006 | | DONE |
|
|
|
|
Telephone call | | | 2/27/2006 | | DONE |
|
|
|
called ###-#### and told Rob permit is ready and fee
|
Alarm Plan Check | | | 2/26/2006 | | PASS |
|
|
|
Plan Modification to add smoke detector for fire/smoke damper control. All fire/smoke dampers will be field verified for smoke detector location and functionality.
Approved pending PDS Fire Inspector field verification. No comments written.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/26/2006 | | DONE |
|
|
|
|
Case Summary | | | 2/24/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 2/24/2006 | | DONE |
|
|
|
|
Issue and Print Permit | | | 1/11/2006 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 12/22/2005 | | 1/10/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 1/10/2006 | | PASS |
|
|
|
Approved pending PDS Fire Inspector field verification. No comments written.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/10/2006 | | |
|
|
|
|
Permit Ready to Issue | | | 1/10/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/10/2006 | | 1/10/2006 | | DONE |
|
|
|
|
Telephone call | | | 1/10/2006 | | DONE |
|
|
|
Spoke with Terie and told her that permit is ready & fees///1/10/06 @2:25pm BAS
|
Case Summary | | | 1/6/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 1/6/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 1/5/2006 | | FAIL |
|
|
|
No written comments. Per telephone coversation with Rob Ahten.
1) Plan sheet indicates BODO #4, 850 W. Broad St. This TI address is BODO #8, 733 W. Borad St.
2) Insufficient visual coverage in the work area.
3) Manual pull station is more than 5' from the front door.
|
Application received | | | 12/22/2005 | | |
|
|
|
|
Case Summary | | | 12/22/2005 | | DONE |
|
|
|
|