Permit Information
Permit NumberFIR05-00898
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 850 W GOWEN RD
Project Namealm - NORCO
Customer Number 
ePlanReview 
Description
To provide a sprinkler monitoring fire alarm system that includes fire/smoke damper control. This also requires an "Emergency Alarm System" (EAS) as defined in 2704.9 IFC (see comment #19) and a "Ventilation System Emergency Shutdown" (VSES) as defined in 2704.3 IFC (see comment #18).

The associated building permit (BLD05-00978) is to construct a new 8,260 square foot, one story, steel framed industrial building to be used as an acetylene gas compressing plant and a 1,950 square foot, steel framed, roof covered dock and related site improvements. The acetylene plant will consist of a 1,360 sq. ft., equipment room, a 285 sq. ft. mechanical room, a 455 sq. ft. office space with single restroom and small break room, a 4,400 sq. ft. charging room and two 880 sq. ft. covered loading docks at the east and west sides of the charging room. This building will be fire sprinklered with the exception of Equipment Room #104 The remote 1,950 sq. ft. covered dock is being reviewed as an outside storage area for hazardous materials. All construction per the approved plans and attached comment list. JCM These buildings were modified to change the building structures from engineer steel to SPECK (pre-engineered steel structures). Acetylene Compressing Plant - Norco
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/3/20064/4/20064/4/2006APASS
DetailsForrest France
Fire alarm issues have been corrected as required, permit finaled.
INSP-Final Inspection3/31/20064/3/20064/3/2006AFAIL
DetailsTroy Cobbley
Zones 2 and 6 are reported as troubles but should be supervisory since they are tamper switches.
INSP-Final Inspection3/30/20063/31/20063/31/2006PFAIL
DetailsTroy Cobbley
Phone line troubles and induct detectors did not report correctly. Need to reverify all zones.
INSP-Final Inspection3/27/20063/29/20063/29/2006PFAIL
DetailsForrest France
Two in-duct detectors failed to function properly, horn in the charging room does not sound the temporal pattern required for fire alarm and conflicts with the temporal pattern of the horn in the office, need to provide NFPA 72 Inspection and Testing form, a copy of central station signal verification of items tested today including panel, sprinkler monitoring, detection and notification devices, alarms, supervisory, and troubles from 3:50 to 5:00 pm today to be available on site at next inspection for review.
INSP-Final Inspection3/23/20063/24/20063/24/2006PFAIL
DetailsForrest France
Two tamper switches at the main control valves are not functional, panel for the local haz mat alarm has no phone line, need to provide completed NFPA 72 inspection and testing form prior to final inspection, no further inspection done at this time.
Permit Ready to Issue  3/20/2006  
Inspection Record Card- Fire3/20/2006 3/20/2006 DONE
Telephone call  3/20/2006  
Informed Jason Minnick (Audio Electronics Inc) ###-#### to pick up permit 3-20-06 eus
Issue and Print Permit  3/20/2006 DONE
Alarm Plan Check  3/19/2006 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  3/19/2006 DONE
Plan assigned to (Mary)12/28/2005 3/19/2006 DONE
Plan resubmittals received  3/10/2006 DONE
Alarm Plan Check  2/21/2006 FAIL
Resubmittal required. Per Thad Mason, Synergy, the emergency alarm system shown on the drawings does not represent the actual system. He will contact AEI
Telephone call  2/16/2006 DONE
Left a message for Thad Mason regarding the missing cut sheets for the emergency alarm detectors and push buttons.
Plan resubmittals received  2/1/2006 DONE
Plan resubmittals received  1/23/2006 DONE
Alarm Plan Check  1/11/2006 FAIL
Resubmittal required which includes the Emergency Alarm System. thad Mason, Jason Minnick have been notified by phone, no written comments.
Telephone call  1/9/2006 DONE
Left a message for Thad Mason (Synergy) regarding the Emergency Alarm System per comment #3 of BLD05-00978.
Application received  12/28/2005  
Case Summary  12/28/2005 DONE