INSP-Final Inspection | 4/3/2006 | 4/4/2006 | 4/4/2006 | A | PASS |
Forrest France
|
|
|
Fire alarm issues have been corrected as required, permit finaled.
|
INSP-Final Inspection | 3/31/2006 | 4/3/2006 | 4/3/2006 | A | FAIL |
Troy Cobbley
|
|
|
Zones 2 and 6 are reported as troubles but should be supervisory since they are tamper switches.
|
INSP-Final Inspection | 3/30/2006 | 3/31/2006 | 3/31/2006 | P | FAIL |
Troy Cobbley
|
|
|
Phone line troubles and induct detectors did not report correctly. Need to reverify all zones.
|
INSP-Final Inspection | 3/27/2006 | 3/29/2006 | 3/29/2006 | P | FAIL |
Forrest France
|
|
|
Two in-duct detectors failed to function properly, horn in the charging room does not sound the temporal pattern required for fire alarm and conflicts with the temporal pattern of the horn in the office, need to provide NFPA 72 Inspection and Testing form, a copy of central station signal verification of items tested today including panel, sprinkler monitoring, detection and notification devices, alarms, supervisory, and troubles from 3:50 to 5:00 pm today to be available on site at next inspection for review.
|
INSP-Final Inspection | 3/23/2006 | 3/24/2006 | 3/24/2006 | P | FAIL |
Forrest France
|
|
|
Two tamper switches at the main control valves are not functional, panel for the local haz mat alarm has no phone line, need to provide completed NFPA 72 inspection and testing form prior to final inspection, no further inspection done at this time.
|
Permit Ready to Issue | | | 3/20/2006 | | |
|
|
|
|
Inspection Record Card- Fire | 3/20/2006 | | 3/20/2006 | | DONE |
|
|
|
|
Telephone call | | | 3/20/2006 | | |
|
|
|
Informed Jason Minnick (Audio Electronics Inc) ###-#### to pick up permit 3-20-06 eus
|
Issue and Print Permit | | | 3/20/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 3/19/2006 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/19/2006 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 12/28/2005 | | 3/19/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 3/10/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 2/21/2006 | | FAIL |
|
|
|
Resubmittal required. Per Thad Mason, Synergy, the emergency alarm system shown on the drawings does not represent the actual system. He will contact AEI
|
Telephone call | | | 2/16/2006 | | DONE |
|
|
|
Left a message for Thad Mason regarding the missing cut sheets for the emergency alarm detectors and push buttons.
|
Plan resubmittals received | | | 2/1/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 1/23/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 1/11/2006 | | FAIL |
|
|
|
Resubmittal required which includes the Emergency Alarm System. thad Mason, Jason Minnick have been notified by phone, no written comments.
|
Telephone call | | | 1/9/2006 | | DONE |
|
|
|
Left a message for Thad Mason (Synergy) regarding the Emergency Alarm System per comment #3 of BLD05-00978.
|
Application received | | | 12/28/2005 | | |
|
|
|
|
Case Summary | | | 12/28/2005 | | DONE |
|
|
|
|