Permit Number | FIR06-00005 |
Status | Finaled |
Name |
AUDIO ELECTRONICS INC
|
Site Address |
12501 W EXPLORER DR
|
Project Name | alm - BOISE RESARCH CENTER |
Customer Number | |
ePlanReview | |
Description |
To provide six (6) duct smoke detectors with remote test switches for HVAC shutdown in the new TI space (Suite 100) and connect them to the existing required sprinkler monitoring fire alarm system. The matrix indicates the signal shall be an alarm. No written comments. Battery calculations appear to be sufficient. Provide updated building map that includes initiating devices and the architectural changes to the PDS Fire Inspector at time of inspection.
The associated building permit (BLD05-03164) is to remodel an existing 5712 sq ft tenant space for new office tenant per approved plans on file. Work to include, removal of interior partitions to create larger open office, construction of new interior partitions, infill roll up exterior door opening, installation of new suspended ceiling system and related lighting, installation of a new roof top HVAC system and related ducting, relocation of an existing breakroom sink, miscellaneous related interior finishes, this building is fully fire sprinklerd. ANY alterations to the sprinkler system and fire alarm system WILL REQUIRE SEPARATE PERMITS. (rmh) *(Sakson & Taylor)*
|