Permit Information
Permit NumberFIR06-00009
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 12754 W LASALLE ST
Project NameSPR LASALLE BLDG
Customer Number 
ePlanReview 
Description
(LASALLE OFFICE BUILDING) This building is fully fire sprinklered for area increase and this permit covers a tenant who is incorporating the entire building. The sprinkler work is to modify then existing shell system for the construction of interior tenant improvements within the entire 16,365-ft/2. The building shell was constructed under permit BLD04-00958 with fire sprinklers installed under FIR04-00582. The fire sprinkler work is related to the installation of interior nonbearing walls, to create 2 restrooms, and two shower rooms, corridors, offices, server room with access floor system, reception area, storage rooms, a breakroom, suspended ceilings and HVAC throughout. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-03340.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/27/20062/27/20062/27/2006PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection2/21/20062/22/20062/22/2006AFAIL
DetailsTroy Cobbley
Could not give final due to missing ceiling tile and two heads that are still overspaced. Sprinkler piping is ok to cover.
INSP-Final Inspection2/20/20062/21/20062/21/2006PFAIL
DetailsTroy Cobbley
Inspection stopped after finding multiple heads overspaced and other heads not installed.
Plan assigned to (Bill)1/30/2006 2/16/2006 DONE
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  2/16/2006 DONE
Inspection Record Card- Fire2/16/2006 2/16/2006 DONE
Permit Ready to Issue  2/16/2006  
Telephone call  2/16/2006  
Informed Shilo Automatic Sprinkler ###-#### to pick up permit 2-16-06 eus
(F) Reprint permit  2/16/2006 DONE
CHANGE STATUS TO (ISS)  2/16/2006 DONE
already issued previously
Plan resubmittals received  1/30/2006 DONE
resubmittals received 5 copies of fire sprinler shop drawings and 5 copies of hydraulic calculations and details.
Plan assigned to (Bill)1/9/2006 1/25/2006 DONE
Sprinkler Plan Check1/9/2006 1/25/2006 PART
DetailsBill Alexander
Re-Submittals Of The Following Items Are Required:
1. Plan is incomplete. The Server #126 room has a raised floor. Fire sprinkler protection will be required under this floor if combustibles are present which includes non rated cabling. Address clarification on the plans to allow for exemption of fire sprinkler protection. (IFC 105.4.2, BMC 7-01-50-IFC 901.2)

2. Plan is incomplete. Accelerator #125 has what appears a ECOH head obstructed between columns D - E and 2 - 3. Provide clarification of construction to determine sprinkler coverage on this plan. (IFC 105.4.2, BMC 7-01-50-IFC 901.2)

3. Plan is incomplete. Within the same vicinity as item 2 above, there are unidentified areas which lacks protection? Provide clarification of occupancy and construction to determine required coverage on this plan. (IFC 105.4.2, BMC 7-01-50-IFC 901.2)

4. Protection missing south of column #3, east of column D. Revise and resubmit. (NFPA 13-8.6.2.2.1, IFC 105.4.2, BMC 7-01-50-IFC 901.2)

5. Protection missing south of column #3, east of column E. Revise and resubmit. (NFPA 13-8.6.2.2.1, IFC 105.4.2, BMC 7-01-50-IFC 901.2)

6. The (unidentified) fire sprinkler riser room lacks protection. Revise and resubmit. (NFPA 13-8.6.2.2.1, IFC 105.4.2, BMC 7-01-50-IFC 901.2)

7. Office #108 does not meet 8.6.2.2. Revise and resubmit. (NFPA 13-8.6.2.2.1, IFC 105.4.2, BMC 7-01-50-IFC 901.2)

8. Janitor #130 spacing exceeds 8.6.2.2. Revise and resubmit. (NFPA 13-8.6.2.2.1, IFC 105.4.2, BMC 7-01-50-IFC 901.2)

9. "Copy Storage #112", "Acctg. Storage #117", "Servers #126", Janitor #130, Accelerator #125 will require more "Occupancy Class" information. (NFPA 13-14.1.3[7], IFC 105.4.2, BMC 7-01-50-IFC 901.2)

10. Provide a required "Fire Sprinkler Upgrade/TI/Remodel Cover Sheet", which is published and can be located at: http://www.cityofboise.org/pds/applications/Fire/TI_Remodel_CoverSheet.pdf.
Inspection Record Card- Fire1/25/2006 1/25/2006 DONE
Permit Ready to Issue  1/25/2006 DONE
Telephone call  1/25/2006 DONE
tlk to lily ###-#### that permit and fees are ready to be picked up
Issue and Print Permit  1/25/2006 DONE
Miscellaneous action  1/24/2006 DONE
Approved written request for early start on this project to drop 1" pipe with plugs to within 1' of the ceiling from existing shell system prior to issuance of approved plans and permit.
Application received  1/9/2006