Permit Number | FIR06-00023 |
Status | Finaled |
Name |
AUDIO ELECTRONICS INC
|
Site Address |
12754 W LASALLE ST
|
Project Name | alm - LASALLE BLDG |
Customer Number | |
ePlanReview | |
Description |
To provide a nine (9) duct smoke detectors with RTSs to RTU 2 through 10 for HVAC shutdown to an existing required sprinkler monitoring fire alarm system which HVAC shutdown. The calculations appear to be sufficient. No written comments, PDS Fire Inspector to field verify functionality of the new duct detectors. An updated building map shall be provided at time of inspection.
The associated building permit (BLD05-01529) is to construct interior tenant improvements within a 16,365 square foot building for a tenant who will occupy the entire building. The building shell was constructed under permit BLD04-00958. Work is to include interior nonbearing walls, 2 restrooms accessible to the disabled, two shower rooms accessible to the disabled, an access floor system, suspended ceilings, and finishes. The work is required to comply with the approved drawings, the plan review report, and all applicable codes. The fire sprinkler system shall comply with NFPA 13 as regulated by the Fire Department. **CJW** (LASALLE OFFICE BUILDING) This building is fire sprinklered for area increase.
|