Permit Information
Permit NumberFIR06-00024
StatusExpired
Name COMMERCIAL FIRE PROTECTION
Site Address 5556 S FEDERAL WAY
Project NameSPR GUERDON ENTERPRISES
Customer Number 
ePlanReview 
Description
GUERDON ENTERPRISES - A PRECONSTRUCTION PHASE* This permit is a "Scope of Work" permit only, limited to the relocation of some 8" existing riser feed main to accommodate a new mezzanine, which will be installed under a separate permit. To relocate an existing 5" feed main that will be above the new mezzanine ceiling, and to install 4 new 8" wet pipe system risers with header, backflow device, wall mounted P.I.'s, FDC and forward flow appurtenance, and (some) 8" main to be capped for future connection and protection of the existing facility, and in association with a new 10,080-ft/2 manufacturing/assembly building. The new (4) risers will not be connected to a water supply installed at a later date, under a separate permitting. Mezzanine fire sprinkler work is not allowed under this permit and will require separate permitting in association with a (mezzanine) building permit. This building is fully sprinklered. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this permit, to provide witness of compliance verification of meeting minimum code. This permit is not attached to any building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permit EXPIRED  8/12/2010 DONE
There are 3 other fire permits at this address FIR06-00782, FIR06-00473, FIR06-00613 by the same contractor that have been finaled. I assumed that this permit was never finaled since it was a "scope of work permit" therefore I am expiring the permit. I did not final this permit since it was a "scope of work permit"
Sprinkler Plan Check8/1/2008 8/13/2008 FAIL
Details
These plans were denied due to missing or lack of information. Upon request, the denied set of plans may be retrieved from my office for salvage. The denied set of plans will be maintained for five working days.
Issue and Print Permit  8/1/2008 DONE
Plan resubmittals received  8/1/2008  
DetailsTisha Gallop
Received three copies of application, submittal packet, plan sheets FP-1, FP-2; taken to fire review
INSP-Final Inspection7/9/20087/9/20087/9/2008ADEFR
DetailsForrest France
Contacted Commercial Fire to provide plan set on site and request permit number for project final as required.
INSP-Sprinkler Rough-in/Hydro1/19/20071/22/20071/22/2007ADEFR
DetailsForrest France
Wrong permit number called in for inspection by the contractor, was intended for FIR06-00782 Guerdon warehouse hydro and OH rough-in.
FIR-Aging Inspection10/31/200610/31/200610/31/2006 DEFR
DetailsForrest France
Plan assigned to (Bill)1/11/2006 1/30/2006 DONE
Sprinkler Plan Check1/11/2006 1/30/2006 PART
DetailsBill Alexander
Re-Submittals Of The Following Items Are Required:
1. Plan submittal is incomplete. No hanger or Seismic information provided. Provide correct and accurate hanger and seismic requirements for the associated work permitted above. (BMC 7-01-50-IFC 901.2 and IFC 105)
PLANS/APPL TAKEN TO FRONT DESK  1/30/2006 DONE
Case Summary  1/30/2006 DONE
Permit Ready to Issue  1/30/2006 DONE
Inspection Record Card- Fire1/30/2006 1/30/2006 DONE
Telephone call  1/30/2006 DONE
left mess that permit is ready
Issue permit  1/30/2006  
Application received  1/11/2006  
Plan assigned to (SAM)8/1/2008    
Inspection Record Card- Fire1/30/2006