Permit Information
Permit NumberFIR06-00031
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 700 N ANCESTOR PL
Project Namealm - Albertson Data Center
Customer Number911310302
ePlanReview 
Description
To provide monitoring of the HVAC shutdown for three Liebert units (duct smoke detectors are "factory" installed, provide cut sheets and installation instructions to the PDS Fire Inspector at inspection). The plans indicate the three "new" units by an address, three additional units are shown with duct detectors. PDS Fire Inspector to field verify these units (as shown on the drawing) are NOT installed. No written comments. Battery calculations appear to be sufficient (the 18 A/H battery is existing, unaware of why it is clouded). Provide revised building map, including any architectural changes to the PDS Fire Inspector at time of inspection.

The associated mechanical permit (MEC05-04220; FNL 12/22/2005) is to install 3 computer room cooling units tied into existing piping & ductwork per initial cert of value $318,668 approved per Lee Rice///12/21/05 BAS
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/17/20064/18/20064/18/2006PPASS
DetailsTroy Cobbley
Fire alarm inspection finaled. The smoke detectors are factory installed and shut the units down.
Inspection Record Card- Fire2/27/2006 2/27/2006 DONE
Permit Ready to Issue  2/27/2006 DONE
Telephone call  2/27/2006 DONE
tlk to charlie bayne ###-#### that permit and fees are ready to be picked up
Issue and Print Permit  2/27/2006 DONE
Alarm Plan Check  2/26/2006 PASS
Approved pending PDS Fire Inspector field verification. No comments written.
PLANS/APPL TAKEN TO FRONT DESK  2/26/2006 DONE
Plan resubmittals received  2/9/2006 DONE
Telephone call  1/30/2006 DONE
Charlie Bayne, Simplex. Question as to why the mechanical permit (MEC05-04220) only indicates 3 units and the FA permit indicates 6 duct detectors.
Alarm Plan Check  1/30/2006 FAIL
Resubmittal required to indicate the correct number of units.
Application received  1/12/2006  
Case Summary  1/12/2006 DONE
Plan assigned to (Mary)1/12/2006