INSP-Final Inspection | 4/7/2006 | 4/10/2006 | 4/10/2006 | A | PASS |
Forrest France
|
|
|
Fire sprinkler work is satisfactory, permit finaled.
|
INSP-Final Inspection | 4/7/2006 | 4/7/2006 | 4/7/2006 | P | FAIL |
Troy Cobbley
|
|
|
Need ceiling tile installed
|
INSP-Final Inspection | 3/20/2006 | 3/21/2006 | 3/21/2006 | A | PART |
Forrest France
|
|
|
Overhead rough-in is acceptable for cover at the drop ceiling areas, final pending installation of ceiling tile and escutcheons.
|
INSP-Final Inspection | 3/16/2006 | 3/17/2006 | 3/17/2006 | A | FAIL |
Forrest France
|
|
|
Various locations are overspaced beyond the maximum design area/density of 148 ft2, overspaced locations are marked on approved plans, one room marked as "file room" shall be spaced for ordinary hazard.
|
Issue and Print Permit | | | 3/10/2006 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 2/15/2006 | | 3/8/2006 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/8/2006 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 2/15/2006 | | 3/8/2006 | | PASS |
Bill Alexander
|
|
|
|
Permit Ready to Issue | | | 3/8/2006 | | |
|
|
|
|
Inspection Record Card- Fire | 3/8/2006 | | 3/8/2006 | | DONE |
|
|
|
|
Telephone call | | | 3/8/2006 | | |
|
|
|
Informed Brad (Treasure Valley Fire Protection) ###-#### to pick up permit 3-8-06 eus
|
INSP-Sprinkler Rough-in/Hydro | 2/22/2006 | 2/22/2006 | 2/22/2006 | P | PART |
Forrest France
|
|
|
Overhead rough-in at the hard lid area adjacent to the elevator lobby is good for cover.
|
Plan resubmittals received | | | 2/15/2006 | | DONE |
|
|
|
|
Sprinkler Plan Check | 1/26/2006 | | 1/30/2006 | | PASS |
Bill Alexander
|
|
|
Plan modification - Add sprinkler protection in the top of the elevator shaft, demo 2 additional heads. Modifying existing main and line (rerouting).
|
Case Summary | | | 1/30/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/30/2006 | | 1/30/2006 | | DONE |
|
|
|
|
Issue and Print Permit | | | 1/30/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 1/25/2006 | | |
|
|
|
|
Plan assigned to (Bill) | 1/17/2006 | | 1/19/2006 | | DONE |
|
|
|
|
Sprinkler Plan Check | 1/17/2006 | | 1/19/2006 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/19/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/19/2006 | | 1/19/2006 | | DONE |
|
|
|
|
Telephone call | | | 1/19/2006 | | DONE |
|
|
|
called Brad
|
Issue and Print Permit | | | 1/19/2006 | | DONE |
|
|
|
|
Application received | | | 1/17/2006 | | |
|
|
|
|