INSP-Final Inspection | 6/6/2006 | 6/7/2006 | 6/7/2006 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 6/2/2006 | 6/5/2006 | 6/5/2006 | A | FAIL |
Troy Cobbley
|
|
|
The wrong heads have been installed in the racks, VK100 instead of VK550, provide one additional EQ brace for the main and provide additional heads for the head box.
|
FIR-Aging Inspection | 5/15/2006 | 5/15/2006 | 5/15/2006 | | NR |
Troy Cobbley
|
|
|
Per Randy the work is done but they are waiting for the new control valve to be wired into the existing alarm system and will call in the inspection when that work is done.
|
Issue and Print Permit | | | 2/13/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/7/2006 | | 2/7/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/7/2006 | | DONE |
|
|
|
|
Telephone call | | | 2/7/2006 | | DONE |
|
|
|
lft vm with randy ###-#### that permit and fees are ready to be picked up
|
Plan assigned to (Bill) | 1/19/2006 | | 2/6/2006 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 1/19/2006 | | 2/6/2006 | | PASS |
Bill Alexander
|
|
|
|
Miscellaneous action | | | 2/6/2006 | | DONE |
|
|
|
Returned documents/plans to permit desk for returning.
|
Telephone call | | | 2/6/2006 | | DONE |
|
|
|
tlk to randy ###-#### that permit has failed and needs to be picked up 8:49 am
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/6/2006 | | DONE |
|
|
|
|
Telephone call | | | 2/3/2006 | | DONE |
|
|
|
Called Randy Bowron and walked through the design problems.
|
Application received | | | 1/19/2006 | | |
|
|
|
|