Permit Information
Permit NumberFIR06-00052
StatusFinaled
Name MICRON TECHNOLOGY INC FA
Site Address 8000 S FEDERAL WAY
Project Namealm -
Customer NumberC9190
ePlanReview 
Description
Fire Alarm System: C9190 Two split system cooling units will be installed in B80, Room 201G. Their purpose is to remove heat load from new I/S equipment. A Vesda high-sensitivity smoke detector will be used to alert fire personnel and shut down the cooling units during a smoke/fire event.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/24/20065/1/20065/1/2006APASS
DetailsForrest France
Vesda system functioned properly, fire alarm passed field inspection.
Alarm Plan Check  3/10/2006 PASS
Approved pending PDS Fire Inspector field verification. No comments written.
PLANS/APPL TAKEN TO FRONT DESK  3/10/2006 DONE
Issue and Print Permit  3/10/2006 DONE
Plan assigned to (Mary)1/20/2006 3/10/2006 DONE
Alarm Plan Check  2/24/2006 FAIL
Resubmittal required. no provision for HVAC shutdown from the FA system based upon the smoke detector in the return of the HVAC unit.
Miscellaneous action  2/16/2006 DONE
Question back to MTI if a mechanical permit is required.
Case Summary  2/13/2006  
Application received  1/20/2006 DONE
This permit was created on the web by Paul Marcolina