Permit Information
Permit NumberFIR06-00053
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 201 W BOISE AVE
Project NameSPR COMET CLEANERS
Customer Number913171801
ePlanReview 
Description
COMET CLEANERS * To install the underground supply and overhead Ordinary Group 1 wet pipe fire sprinkler system for a 3,100-ft/2 tenant in a V-B strip mall referenced as Pennsylvania Station. Fire sprinkler work shall be per plans (which may include red-lined notes), attached plan review conditions/comments, IFC 2003, NFPA 13-2002 and 72, as regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is not attached to any other permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/21/20064/24/20064/24/2006APASS
DetailsForrest France
Fire sprinkler work passed final inspection.
INSP-Sprinkler Rough-in/Hydro4/20/20064/21/20064/21/2006PPART
DetailsForrest France
Hydrostatic test for the UG supply and the overhead system both passed inspection. Rough-in inspection is satisfactory as well, need to provide a ball drip at the FDC, and signage at the FDC per review notes.
INSP-Supply line flush4/12/20064/13/20064/13/2006APART
DetailsForrest France
UG supply line flush performed satisfactory, the PIV has been adjusted to the required height above finish grade.
INSP-Supply line flush4/7/20064/11/20064/11/2006PDEFR
DetailsForrest France
No time available to complete this inspection today, to be rescheduled per conversation with contractor.
INSP-Sprinkler Rough-in3/27/20063/28/20063/28/2006AFAIL
DetailsForrest France
The yard post indicator is below min. height requirements above finish grade, need to cap ductile riser piece, provide seismic clearance at floor slab. Thrust blocks are acceptable, the majority of UG pipe run was covered prior to inspection.
Sprinkler Plan Check2/23/2006 3/17/2006 PASS
DetailsBill Alexander
Plan assigned to (Bill)2/22/2006 3/17/2006 DONE
PLANS/APPL TAKEN TO FRONT DESK  3/17/2006 DONE
Telephone call  3/17/2006  
Informed Curtis (Simplex/Grinnell) ###-#### to pick up permit 3-17-06 eus
Inspection Record Card- Fire3/17/2006 3/17/2006 DONE
Permit Ready to Issue  3/17/2006  
Issue and Print Permit  3/17/2006 DONE
Plan resubmittals received  2/23/2006  
Issue and Print Permit  2/15/2006 DONE
Plan assigned to (Bill)1/20/2006 2/9/2006 DONE
Sprinkler Plan Check1/20/2006 2/9/2006 PART
DetailsBill Alexander
Corrections Required:
1. An exterior indicating control valve meeting minimum 13-8.1.2, 24-2.2.6, 6.3.1, 6.3.3.2 requirements, shall be provided for this facility. If this is not provided, then a 1 (one) hour fire rated construction sprinkler control room must be provided with an approved outside clear door access. All control valves on fire sprinkler systems must be unobstructed, immediately discernible and accessible. The control handles must be installed between two (2'-0") and five (5'-0") feet above finished grade. Post indicators shall be set so that the top of the post will be 36" above the final grade. (NFPA 13-8.15.1.3, IFC 102.7)

2. Designer submitted a Sammy® (Speedy Products) sheet addressing connections to TJI's. Plans do not reference any TJI's in the building? Connection to TJI's must meet the manufacturer's installation of the same which are limited as to hanger connections AND the pipe size supporting. Connections for seismic requirements are also reference in the manufacturer's installation guides. Designer shall provide correct clarification and details of the TJI's, the hanger connections and seismic attachments incorporating, which meet the manufacturer's requirements, on the plans. (BMC 7-01-50-901.2, IFC 105.4.2)

3. Provide correct dimensioning or and approved scale of the riser from the floor. (BMC 7-01-50 IFC 901.2, IFC 105.4.2)

4. It is assumed that all inside wall penetrations are through "frangible" walls. If not, then corrections addressing the wall locations and minimum penetration/flexible requirements shall be included on the plans. (NFPA 13-9.3.2*, 9.3.3*, A.9.3.3, A.9.3.2, 14.1.3 (21)

5. Designer must show type and location of all required, not required joints (flexible & ridgid) and fitting on the mains and lines. (BMC 7-01-50 IFC 901.2, IFC 105.4.2, NFPA 13-14.1.3 [21])

6. Provide size of city main in the street and whether it is dead-end or circulating. (NFPA 13-14.1.3 (10)
PLANS/APPL TAKEN TO FRONT DESK  2/9/2006 DONE
Inspection Record Card- Fire2/9/2006 2/9/2006 DONE
Permit Ready to Issue  2/9/2006 DONE
Telephone call  2/9/2006  
Left message forTom Easton ###-#### that permit is ready to be picked up
Plan resubmittals received  1/31/2006  
Application received  1/20/2006  
Case Summary  1/20/2006 DONE