Permit NumberFIR06-00055
StatusFinaled
Name FUTURETECH
Site Address 11580 W FAIRVIEW AVE
Project Namealm - COLTRIN BLDG
Customer Number 
ePlanReview 
Description
To provide a required sprinkler monitoring fire alarm system that includes HVAC shutdown and elevator recall/shutdown.

The associated building permit (BLD 04-02020) is to construct a 18,490 sq. ft. two story type VB fully fire sprinklered office/retail shell building. Other work includes all site improvements, paving and landscaping per approved plans and attachments, DRH04-124. No occupancy is authorized by this permit. Separate plans and permits are required for each tenant space. Fire sprinklers are used for area and story increase. First floor 14,000 sq. ft, 2nd floor 4,490 sq. ft. Coltrin Building (Shell) -

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/7/20062/7/20062/7/2006PPASS
DetailsTroy Cobbley
Fire alarm permit finaled
INSP-Alarm Testing2/6/20062/7/20062/7/2006APASS
DetailsTroy Cobbley
Fire alarm permit finaled
INSP-Alarm Testing2/3/20062/3/20062/3/2006PPART
DetailsTroy Cobbley
Need atleast 10.25AH batteries for the facp. Need to test duct detectors and elevator recall. Need nfpa 72 forms and copy of signals.
Issue and Print Permit  1/31/2006  
Plan assigned to (Mary)1/23/2006 1/30/2006 DONE
Application received  1/30/2006 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  1/30/2006 DONE