Case Summary | | | 5/13/2008 | | DONE |
|
|
|
|
INSP-Final Inspection | 11/9/2006 | 11/9/2006 | 11/9/2006 | P | PASS |
Forrest France
|
|
|
Fire sprinkler work is complete, permit finaled.
|
INSP-Final Inspection | 11/6/2006 | 11/7/2006 | 11/7/2006 | P | PART |
Forrest France
|
|
|
Items from previous inspection verified for completion, forward flow completed, okay for final when ball drip and FDC caps are installed.
|
INSP-Final Inspection | 10/25/2006 | 10/26/2006 | 10/26/2006 | A | CANC |
Troy Cobbley
|
|
|
No time for inspection today.
|
INSP-Sprinkler Rough-in/Hydro | 6/6/2006 | 6/7/2006 | 6/7/2006 | A | PART |
Troy Cobbley
|
|
|
Above ground hydro test passed. Sprinkler rough-in failed due to the upright sprinkler heads not meeting NFPA 13 8.6.5.2.1.6 and 8.6.5.2.1.7. Also the sprinkler heads are overspaced at the west end of the sprinkler system.
|
INSP-Sprinkler Rough-in | 4/10/2006 | 4/11/2006 | 4/11/2006 | A | PART |
Troy Cobbley
|
|
|
Canopy is ok to cover but one upright sprinkler head is overspaced from the west end of the central big canopy. See marked plans for exact location.
|
INSP-Sprinkler Rough-in | 4/7/2006 | 4/10/2006 | 4/11/2006 | A | PART |
Troy Cobbley
|
|
|
Canopy is ok to cover but one upright sprinkler head is overspaced from the west end of the central big canopy. See marked plans for exact location.
|
INSP-Sprinkler Rough-in | 4/6/2006 | 4/7/2006 | 4/7/2006 | A | CANC |
Troy Cobbley
|
|
|
Inspection was supposed to be scheduled for monday.
|
Sprinkler Plan Check | 3/14/2006 | | 3/31/2006 | | PASS |
Bill Alexander
|
|
|
|
Miscellaneous action | | | 3/31/2006 | | DONE |
|
|
|
Took corrected permit submittals to permit desk for calling and distributing.
|
Miscellaneous action | | | 3/31/2006 | | DONE |
|
|
|
permit picked up, no fee
|
(F) Reprint permit | | | 3/31/2006 | | |
|
|
|
|
Plan resubmittals received | | | 3/14/2006 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 1/26/2006 | | 2/21/2006 | | DONE |
|
|
|
|
Sprinkler Plan Check | 2/17/2006 | | 2/21/2006 | | PART |
Bill Alexander
|
|
|
Re-Submittals Of The Following Items Are Required:
1. Fire department connections shall be on the street side of buildings, immediately discernible, fully visible and recognizable from the street or nearest point of fire department apparatus access. Relocate FDC to a location that faces either S. Milwaukee or Overland. Pipe sizing shall be equivalent to requirements of NFPA 13. (IFC 912.2.1, BMC 7-01-50-IFC 901.2)
2. Designer give construction information on the roof membrane yet does not address the fire sprinkler riser room meeting requirements specifically addressed in, Boise Municipal Code 7-01-53 CONTROL VALVE LOCATION - IFC Section 903.1.3? Provide required riser room construction, door information and signage and resubmit. (BMC 7-01-50-IFC 901.2).
3. Designer shows a section detail addressing TJL's, with hanger detail addressing TJI's? Provide clarification of construction in this facility and address correct (manufacturers) attaching requirements for the required listed hanger attaching devises. Each shall coordinate with the other and meet both the manufacturer and NFPA 13 Chapter 9. That information shall be included on the plans. (BMC 7-01-50-IFC 901.2).
4. Provide an auxiliary drain as needed to the 2" far main per requirements of NFPA 13-5 14.2.5 and show it on the plan. (BMC 7-01-50-IFC 901.2).
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/21/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/21/2006 | | 2/21/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/21/2006 | | |
|
|
|
|
Telephone call | | | 2/21/2006 | | |
|
|
|
Informed Trent (Shilo Automatic Sprinkler) ###-#### to pick up permit 2-21-06 eus
|
Issue and Print Permit | | | 2/21/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 2/17/2006 | | DONE |
|
|
|
Shilo used the wrong Building Permit.
|
Sprinkler Plan Check | 1/28/2006 | | 2/16/2006 | | FAIL |
Bill Alexander
|
|
|
This permit is attached to a demolition burn permit. No other BLD associated at the address. Returned plans to permit desk. Contacted Trent Bice indicating correction required.
|
Miscellaneous action | | | 2/16/2006 | | DONE |
|
|
|
Emailed Trent Bice indicating this fire permit is associated with a BLD Demo Permit for a residential burn. No other BLD associated with this address. Returned documents to permit desk for returning.
|
Telephone call | | | 2/16/2006 | | DONE |
|
|
|
left mess that permit has incorrect bld # & need to pickup
|
Telephone call | | | 2/16/2006 | | DONE |
|
|
|
gave plans to customer had wrong bld #
|
Application received | | | 1/26/2006 | | |
|
|
|
|