Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberFIR06-00082
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 8800 W EMERALD ST
Project Namealm - HEALTHSOUTH TVH
Customer Number 
ePlanReview 
Description
The pre-action sprinkler system for this space was modified, see scope below for FIR06-00034. New smoke detectors are being provided in the control room, under the floor in the MRI room and under the floor in the computer room to an existing zone on the pre-action panel (Notifier, RP-1001). The pre-action system is a double-interlock and requires both smoke and lo-air for actuation. Three fire/smoke dampers are being installed in the wall of the control room to the corridor, these are 120VAC and will be monitored by the building fire alarm control panel. An additional door hold-open is being installed at the control room door, it will be connected to an existing circuit.

The associated building permit (BLD 05-03256) is to remodel a portion of the existing hospital (northwest corner) to allow for a replacement of the existing MRI unit with a new MRI unit & equipment room per approved plans. To convert use of storage room 103 to MRI equipment room; and to convert tech service area 104 into file storage area. To install raised access floor in new MRI equipment room and portion of MRI room; upgrade concrete floor at new MRI unit; new smoke partition walls at new file storage room 104 W/ self closing, rated door; modify electrical, mechanical, plumbing, sprinkler & alarm systems to meet tenant needs and comply with current adopted codes and ordinances. drs (HEALTHSOUTH TREASURE VALLEY HOSPITAL)(MRI SUITE)

The associated sprinkler permit (FIR06-00034) is to remove and plug 4 existing heads and copper piping, and reinstall 4 new SSP's and copper piping for a replacement of the existing MRI unit with a new MRI unit, relocate 13 existing SSP's and add 4 SSP's to allow & equipment room; the conversion of storage room #103 to MRI equipment room and tech service area #104 into file storage area and the installation of new smoke partition walls at new file storage room #104, for the remodel of a portion of the existing hospital located in the northwest corner. Work not addressed in the fire protection permit is the installation of a raised access floor in new MRI equipment room and portion of MRI room and upgrade concrete floor at new MRI unit. Fire sprinkler work in the MRI unit room shall be in accordance with minimum requirements of IFC-2003, and attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this permit, to provide witness of compliance verification of meeting minimum code. This permit is attached to BLD05-03256. HEALTHSOUTH TREASURE VALLEY HOSPITAL-MRI SUITE)
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/25/20067/26/20067/26/2006PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection7/7/20067/7/20067/7/2006PFAIL
DetailsTroy Cobbley
Provide smoke detection for the Liebert unit and test the remaining two induct smoke detectors.
INSP-Final Inspection7/5/20067/5/20067/6/2006PCANC
DetailsTroy Cobbley
earl ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
FIR-Aging Inspection7/3/20067/3/20067/5/2006 NR
DetailsTroy Cobbley
work is in progress
Inspection Record Card- Fire4/3/2006 4/3/2006 DONE
Permit Ready to Issue  4/3/2006 DONE
Telephone call  4/3/2006 DONE
called ###-#### and told John that permit is ready and fee
Issue and Print Permit  4/3/2006 DONE
Plan assigned to (Mary)2/2/2006 3/31/2006 DONE
Alarm Plan Check  3/31/2006 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  3/31/2006 DONE
Alarm Plan Check  3/29/2006 FAIL
FACP battery calculations are incorrect. Verification is required for the duct smoke detector power (24VDC as the battery calcs show, or 120 VAC as stated by John). If the duct detectors are powered by the panel, the batteries will need to be upgraded and a compatibility listing for the smoke to the FACP is required. If the duct smoke detetors are 120VAC powered, a revised battery calculation is required.
Telephone call  3/24/2006 DONE
Called John Lopez, he was out of the office for the day, I said I would call back on Monday.
Telephone call  3/23/2006 DONE
Request to John Lopez for smoke detector cut sheets and compatibility listing for the RP1000 panel. He said he would fax them to Boise City.
Telephone call  3/23/2006 DONE
Left a message that the battery calculations for the main FACP indicated an upgrade of the batteries if the in-duct dtectors are to be powered by the panel. A compatibility listing would be requried.
Plan resubmittals received  3/10/2006 DONE
Meeting  3/9/2006 DONE
Don from Russell brought plans to clear up the issues. See the comments under "fire alarm permit", dated 3/9
Alarm Plan Check  3/9/2006 FAIL
COMPLETE RESUBMITTAL IS REQUIRED (2 sets and all documentation). No written comments. The following needs to be addressed:

1) Define the entire space of the existing double interlock pre-action system.

2) Re-define the initiating devices to report to the appropriate panel. (unless the initiating device is in the pre-action space, it should NOT report to the pre-action releasing panel.)

3) Ensure there is a smoke detector over the RP1001 panel.

4) Evaluate the type of detectors being installed in specific spaces.

These comments have been faxed to Jon Van Stone (E2) and John Lopez (Fire Sentry)
Case Summary  3/9/2006  
Telephone call  3/7/2006 DONE
Called John Lopez. Asked why heats were installed as opposed to smokes, (Earl stated it was probably because of the magnet.) then why would you install a smoke detector in the space?

Is there a barrier between the two rooms under the floor?
Telephone call  3/3/2006 DONE
Shawn Meador called, the smoke detector is to be placed under the floor. Does not know if there is a barrier, does not know why there are heat detectors existing.
Telephone call  3/1/2006 DONE
Phone message from Shawn Meador E2, I called him back and left a message.
Telephone call  2/17/2006 DONE
Left a message for Jon Van Stone to call me regarding the design of the system.
Application received  2/2/2006