INSP-Final Inspection | 6/4/2012 | 6/4/2012 | 6/4/2012 | P | PASS |
Forrest France
|
|
|
Hood suppression permit finaled.
|
FIR-Aging Inspection | 6/4/2012 | 6/4/2012 | 6/4/2012 | | DONE |
Forrest France
|
|
|
Hood suppression system is now monitored by the building FACP. Permit okay for final.
|
FIR-Aging Inspection | 1/25/2012 | 1/25/2012 | 2/1/2012 | | NR |
Troy Cobbley
|
|
|
I forwarded information to Romeo Gervais for further action.
|
FIR-Aging Inspection | 6/20/2011 | 6/20/2011 | 6/20/2011 | | FAIL |
Forrest France
|
|
|
Ref. correction items.
|
FIR-Aging Inspection | 12/6/2010 | 12/6/2010 | 12/8/2010 | | FAIL |
Forrest France
|
|
|
Requires fire alarm interconnect.
|
FIR-Aging Inspection | 10/6/2010 | 10/6/2010 | 10/6/2010 | | FAIL |
Forrest France
|
|
|
Ref. activity notes 5/27
|
FIR-Aging Inspection | 8/6/2010 | 8/6/2010 | 8/10/2010 | | FAIL |
Forrest France
|
|
|
|
FIR-Aging Inspection | 5/27/2010 | 5/27/2010 | 5/27/2010 | | PART |
Forrest France
|
|
|
Final pending verification of interconnection to the building fire alarm system.
|
INSP-Final Inspection | 2/13/2006 | 2/21/2006 | 2/21/2006 | A | PART |
Forrest France
|
|
|
The hood suppression system functioned under test conditions, however the following items need to be addressed prior to final approval; provide a junction box for the power supply adjacent to the Ansul cabinet, the hood canopy must meet distance requirements for a minimum 6" extension beyond the cooking surface edge, holes in the hood must be properly sealed, where buildings are equipped with a fire alarm panel the hood suppression system must be monitored.
|
Application received | | | 2/3/2006 | | |
|
|
|
|
Issue and Print Permit | | | 2/3/2006 | | DONE |
|
|
|
|