INSP-Final Inspection | 3/10/2006 | 3/10/2006 | 3/10/2006 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Sprinkler Rough-in | 3/9/2006 | 3/10/2006 | 3/10/2006 | A | PASS |
Forrest France
|
|
|
Fire sprinkler work is satisfactory.
|
Sprinkler Plan Check | 2/24/2006 | | 3/1/2006 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/1/2006 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 2/9/2006 | | 3/1/2006 | | DONE |
Bill Alexander
|
|
|
|
Plan resubmittals received | | | 2/24/2006 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 2/9/2006 | | 2/22/2006 | | FAIL |
Bill Alexander
|
|
|
Re-Submittals Of The Following Items Are Required:
1. Provide listing of sprinkler incorporating the listing with the proposed water shield (correlating with each). (NFPA 13-8.13.3.2, BMC 7-01-50-IFC 901.2, IFC 105.4.2)
2. Provide data submittals on control valve. Valve shall meet requirements of 6.7.1.2. (BMC 7-01-50-IFC 901.2, IFC 105.4.2)
3. Provide data submittals on tamper (supervision) switch. (BMC 7-01-50-IFC 901.2, IFC 105.4.2)
4. Provide correct hanger requirements meeting IBC 102.4, 102.7, 102.8, 104.7.2, 105.4.2, 1604.3, 1604.4, NFPA 13-9.1.1.2, 9.2.3.2.1, 9.2.3.5*, BMC 7-01-50-IFC 901.2, IFC 105.4.2).
|
Application received | | | 2/9/2006 | | DONE |
|
|
|