INSP-Final Inspection | 10/24/2006 | 10/24/2006 | 10/24/2006 | P | PASS |
Forrest France
|
|
|
Fire alarm passed final inspection.
|
INSP-Alarm Testing | 10/20/2006 | 10/23/2006 | 10/23/2006 | P | CANC |
Forrest France
|
|
|
Inspection rescheduled due to time constraints.
|
INSP-Final Inspection | 7/26/2006 | 7/27/2006 | 7/27/2006 | A | PART |
Troy Cobbley
|
|
|
A temporary occupancy was given until the south tenant is complete
|
INSP-Final Inspection | 7/25/2006 | 7/25/2006 | 7/25/2006 | P | FAIL |
Troy Cobbley
|
|
|
Tamper switch on the riser #2 did not operate and the gas was not turned on for the hvac units for the testing of the duct smoke detectors. Signals should be redone since four alarm signals were sent but only three had been received at the monitoring agency.
|
FIR-Aging Inspection | 5/30/2006 | 5/30/2006 | 6/1/2006 | | NR |
Troy Cobbley
|
|
|
work in progress
|
Issue and Print Permit | | | 2/28/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/27/2006 | | 2/27/2006 | | DONE |
|
|
|
Reprint with correct address 2-27-06 eus
|
Telephone call | | | 2/27/2006 | | |
|
|
|
Informed Brent (Crane Alarm) to pick up permit 2-27-06 eus
|
Plan assigned to (Mary) | 2/13/2006 | | 2/24/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 2/24/2006 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/24/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/24/2006 | | |
|
|
|
|
Inspection Record Card- Fire | 2/24/2006 | | 2/24/2006 | | DONE |
|
|
|
|
Case Summary | | | 2/13/2006 | | DONE |
|
|
|
|
Application received | | | 2/13/2006 | | |
|
|
|
|