INSP-Final Inspection | 5/31/2006 | 6/1/2006 | 6/1/2006 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. Duct detectors mounting position verified ok with pressure differential testing with TVR.
|
INSP-Final Inspection | 5/31/2006 | 5/31/2006 | 5/31/2006 | P | FAIL |
Troy Cobbley
|
|
|
PIV is not wired up or shown on the plans and the duct smoke detector problems have not been addressed yet.
|
INSP-Final Inspection | 5/26/2006 | 5/30/2006 | 5/30/2006 | P | FAIL |
Troy Cobbley
|
|
|
Troy, We would like to schedule for sometime in the afternoon. Please call us when you have a time. Jason, Mike, or Ken; Phone #: ###-#### Internet Inspection Request from: Jason Minnick
No inspection performed:
7 ea. duct detectors are not installed per manufacturer's installation requirements. Inspector will accept differential reading (inspector verifies) or third party measurements.
|
Permit Ready to Issue | | | 3/21/2006 | | DONE |
|
|
|
|
Issue permit | | | 3/21/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/20/2006 | | 3/20/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 3/19/2006 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/19/2006 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 2/21/2006 | | 3/19/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 3/6/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 3/4/2006 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Jason Minnick.
|
Application received | | | 2/21/2006 | | |
|
|
|
|
Case Summary | | | 2/21/2006 | | DONE |
|
|
|
|