Permit Information
Permit NumberFIR06-00136
StatusFinaled
Name MICRON TECHNOLOGY INC FA
Site Address 8000 S FEDERAL WAY
Project Namealm -
Customer NumberC8945
ePlanReview 
Description
Fire Alarm System: C8945 The remodel of the clean and non-clean bench areas will require modification of the existing fire alarm system in Building 24D. The cleanroom air handling will be supplemented by the addition of a fan powered hepa grid, and a Vesda Laser Scanner will be added to the system for fire alarm initiation. A shunt trip activated by the fire alarm system will shutdown the fan powered hepas in the event of smoke detection. Horn / Strobe coverage will be adjusted per the remod
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/19/20073/20/20073/20/2007APASS
DetailsForrest France
Fire alarm work passed inspection, permit finaled.
INSP-Final Inspection2/27/20072/28/20072/28/2007ADEFR
DetailsForrest France
Inspection to be rescheduled.
INSP-Final Inspection10/30/200611/1/200611/1/2006APART
DetailsForrest France
Per inspection by M. Timmerman the AV portion of work for this permit in the fab level is satisfactory.
Plan assigned to (Mary)2/24/2006 6/30/2006 DONE
Alarm Plan Check  6/30/2006 PASS
Approved pending PDS Fire Inspector field verification. No comments written.
PLANS/APPL TAKEN TO FRONT DESK  6/30/2006 DONE
Issue and Print Permit  6/30/2006 DONE
Alarm Plan Check  6/26/2006 FAIL
Resubmittal required. New corridors created do not have sufficient visuals.
Miscellaneous action  5/26/2006 DONE
Plans not ready...no changes
Miscellaneous action  4/28/2006 DONE
Plans NOT ready yet.
Alarm Plan Check  4/4/2006 FAIL
Provide the following information:

1) ceiling heights (FA2.1.1)
2) existing pull stations shown on demo, but not included on new
3) existing smoke for BPS3.3 shown on dem, but not included on new
4) FA2.2.1, H/S demoed, new wall appears that the mid section of room 101E has no coverage.
Application received  2/24/2006 DONE
This permit was created on the web by Paul Marcolina
Inspection11/1/200611/1/2006   
Conducted A/V Inspection Only Fab Level. Inspection by Mike Timmerman 11/1/2006. Remaining will need to be completed on next inspection.