INSP-Final Inspection | 5/25/2006 | 5/26/2006 | 5/26/2006 | A | PASS |
Forrest France
|
|
|
Contact: Todd; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
Sprinkler Inspection card is missing.
|
DOC - Permit Finaled | | | 5/26/2006 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in | 4/27/2006 | 4/27/2006 | 4/27/2006 | P | PART |
Forrest France
|
|
|
The fireproofing at the hangers has been repaired, overhead sprinkler is acceptable for cover at the hard lid areas.
|
INSP-Sprinkler Rough-in/Hydro | 4/25/2006 | 4/26/2006 | 4/26/2006 | A | FAIL |
Troy Cobbley
|
|
|
Need to repair the fire proofing that has been removed for the installation of pipe hangers.
|
Telephone call | | | 4/24/2006 | | DONE |
|
|
|
tlk to receptionist that permit and fees are ready to be picked up
|
(F) Reprint permit | | | 4/24/2006 | | DONE |
|
|
|
|
Telephone call | | | 4/20/2006 | | DONE |
|
|
|
Telcon from Scott @ Sparks GC inquiring on status of resubmittal. Explained basis of our policy. I suggested he might ask DeBest if they are willing to request this job be moved ahead of another one of their jobs, and if they are willing to do that, they can call and discuss with Bill.
|
Plan resubmittals received | | | 4/13/2006 | | |
|
|
|
Plan modification to show dropped hard ceiling in dining room, added by architect after sprinkler design.
|
Plan assigned to (Bill) | 3/2/2006 | | 3/21/2006 | | DONE |
|
|
|
|
Sprinkler Plan Check | 3/2/2006 | | 3/21/2006 | | PASS |
Bill Alexander
|
|
|
Corrections/Verifications Required
1. Viking VK180, VK300, VK302, VK305, VK404, VK606, Tyco TY5332, sprinklers are not listed for pressures in excess of 175 psi. This tenant shall be fitted with approve SSU fire sprinklers that meet the shell systems current performance pressure performance design available with IFC Fire/Life Safety Inspector verifying by submittals and installation matching the same. (NFPA 13-6.13)
2. All pipe and fittings incorporating in this tenant shall also be required to meet the 13-6.1.3 and 6.4.4. Data submittals shall also be required to the IFC Fire/Life Safety Inspector matching the existing and new modification addressed under this permit.
3. This facility has a fire pump and maximum static or flowing pressure exceeds 100 psi. Branch line above a ceiling supplying pendent sprinklers below the ceiling shall have hanger assemblies on all ends or offset sprinkler, to prevent upward movement of the pipe. (NFPA 13-9.2.3.4.3.1)
4. Occupancy is not permitted until FIR05-00425 incorporating the High Rise fire protection, which includes the secondary water supply, has been finaled.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/21/2006 | | |
|
|
|
|
Inspection Record Card- Fire | 3/21/2006 | | 3/21/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/21/2006 | | DONE |
|
|
|
|
Telephone call | | | 3/21/2006 | | |
|
|
|
lft ms with receptionist due catherine sosa no longer works there ###-#### that permit and fees are ready to be picked up
|
Issue and Print Permit | | | 3/21/2006 | | DONE |
|
|
|
|
Application received | | | 3/2/2006 | | |
|
|
|
|