Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR06-00149
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 2315 E ROANOKE DR
Project NameSPR WALLACE CONST RESIDENCE
Customer Number 
ePlanReview 
Description
WALLACE CONSTRUCTION-RESIDENCE * To install a (modified) life safety NFPA 13D system in a four bedroom, three and quarter bathroom 3098-ft/2 three story single family dwelling (593-ft/2 first floor, 1392-ft/2 second floor, 1113-ft/2 third floor) with a attached 1120-ft/2 three car garage. new four bedroom, three and half bath, 3381-ft/2 two story single family dwelling (2941-ft/2 first floor & 440-ft/2 second floor, 893-ft/2 three car garage). The modification is the installation of a single row dry sidewall sprinklers along the common wall attached to the garage and the living space. System shall be equipped with an alarm initiating device and an outside alarm. All fire sprinkler work and related, which includes dual service water supply, the system backflow prevention device (both provided and installed by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD05-00983.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/7/20068/8/20068/9/2006PPASS
DetailsForrest France
One painted SW head replaced while on site, final fire sprinkler inspection passed.
INSP-Sprinkler Rough-in4/10/20064/11/20064/11/2006PPART
DetailsForrest France
Overhead rough-in is good for cover, field modifications such as added heads at some locations due to obstructions which do not show on the approved plan must be reflected on as-built drawings, be aware of possible light fixture obstructions at some areas, UG supply line flush performed satisfactory.
INSP-Sprinkler Rough-in4/6/20064/7/20064/7/2006PFAIL
DetailsForrest France
Approved plans not available for verification of field installation, no contractor on site at the time of inspection.
Issue and Print Permit  3/24/2006 DONE
Plan assigned to (Bill)3/3/2006 3/23/2006 DONE
Sprinkler Plan Check3/3/2006 3/23/2006 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  3/23/2006 DONE
Inspection Record Card- Fire3/23/2006 3/23/2006 DONE
Permit Ready to Issue  3/23/2006 DONE
Telephone call  3/23/2006 DONE
left mess that permit is ready
Case Summary  3/3/2006 DONE
Application received  3/3/2006