Permit Information
Permit NumberFIR06-00161
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 1897 N WILDWOOD ST
Project NameSPR STEELWOOD FLEX CONDOS
Customer Number 
ePlanReview 
Description
STEEL WOOD FLEX. CONDOS. (SHELL BUILDING #3) - To construct a new 5,550-ft/2, one story, office shell building constructed of masonry exterior wall, concrete slab floor and wood truss roof system. This building will be fully fire sprinklered to meet fire water flow requirements. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The underground fire service supply was permitted under FIR06-00078. This permit is attached to building permit: BLD05-01262. This is a cold shell building permit only. This and the underground service supply must be finaled prior to any following and or associated tenant improvement permits. No occupancy is allowed under this permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/21/20073/22/20073/23/2007PPASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in/Hydro7/25/20067/26/20067/26/2006PCANC
DetailsTroy Cobbley
Wrong inspection type called in. Should be for a final.
INSP-Final Inspection7/26/20067/26/20067/26/2006PPART
DetailsTroy Cobbley
A temporary occupancy is approved with dave hanniman's permission until the south tenant space has been completed.
FIR-Aging Inspection6/30/20066/30/20067/5/2006 NR
DetailsTroy Cobbley
work is in progress
Sprinkler Plan Check4/10/2006 5/1/2006 PASS
DetailsBill Alexander
Miscellaneous action  5/1/2006 DONE
Took approved plans to permit desk for retunring. 2nd Review-No Fee.
Inspection Record Card- Fire5/1/2006 5/1/2006 DONE
Permit Ready to Issue  5/1/2006 DONE
Telephone call  5/1/2006 DONE
called ###-#### and left message for Randy Bowron that permit is ready and fee
CHANGE STATUS TO (ISS)  5/1/2006 DONE
(F) Reprint permit  5/1/2006 DONE
Plan resubmittals received  4/10/2006  
Issue and Print Permit  3/31/2006 DONE
Plan assigned to (Bill)3/8/2006 3/30/2006 DONE
Sprinkler Plan Check3/9/2006 3/30/2006 PART
DetailsBill Alexander
Re-Submittals Of The Following Items Are Required:
1. FP1. Riser shall be provided with minimum dimensioning on it. Some critical required dimensioning is floor to center of the system riser piping, an acceptable FDC (w/elevations), critical listing installation requirements for the flow switch, etc. It would wise and helpful to include pipe sizing (not just as related in the riser keyed notes).

2. FP.1. Provide/Finish elevation dimensioning of the FP1 Section "A-A" and "B-B" on FP1.

3. Since the designer has submitted one package for 4 permits, provide a floor plan that addresses the (proposed) tenant T.I.'s in regard to locations and wall boundaries.
PLANS/APPL TAKEN TO FRONT DESK  3/30/2006 DONE
Inspection Record Card- Fire3/30/2006 3/30/2006 DONE
Permit Ready to Issue  3/30/2006 DONE
Telephone call  3/30/2006 DONE
called ###-#### and left message for Randy with Alicia that permit is ready and fees
Telephone call  3/27/2006 DONE
2:30 pm. Call De Best Fire Protection and talked to Matt regarding this project. Building permit attached is a a shell permit and plans submitted is complete shell and T.I. Address has no shell work associated. Address on the permit application does not match the building permit? He said he will check it out get back with me.
Application received  3/8/2006