Sprinkler Plan Check | 7/18/2006 | | 7/27/2006 | | DONE |
Bill Alexander
|
|
|
|
INSP-Final Inspection | 7/14/2006 | 7/14/2006 | 7/14/2006 | P | PASS |
Troy Cobbley
|
|
|
Fire sprinkler permit finaled
|
INSP-Final Inspection | 7/12/2006 | 7/13/2006 | 7/13/2006 | A | FAIL |
Troy Cobbley
|
|
|
Corrections as noted on the previous inspection have been taken care of but the contractor did not have the approved plans on site so that the inspection could be continued.
|
Plan resubmittals received | | | 7/12/2006 | | |
|
|
|
|
INSP-Final Inspection | 7/6/2006 | 7/7/2006 | 7/7/2006 | P | FAIL |
Forrest France
|
|
|
Noted several issues including overspaced head, blocked coverage by ductwork in several locations, incorrect temp ratings at the kitchen hood area, missing ssp in the mech. closet, one head with bent deflector needs to be replaced, min. spacing between heads is exceeded at one location. Inspection concluded at the first floor due to number of defficiencies, no inspection done for the basement area at this time.
|
INSP-Final Inspection | 7/6/2006 | 7/7/2006 | 7/6/2006 | A | CANC |
Forrest France
|
|
|
Final Inspection; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|
CHANGE STATUS TO (ISS) | | | 7/5/2006 | | DONE |
|
|
|
plans picked up no fees
|
(F) Reprint permit | | | 7/5/2006 | | DONE |
|
|
|
|
(F) Reprint permit | | | 7/5/2006 | | DONE |
|
|
|
|
Sprinkler Plan Check | 6/16/2006 | | 6/30/2006 | | PASS |
Bill Alexander
|
|
|
|
Miscellaneous action | | | 6/30/2006 | | DONE |
|
|
|
Took revised plans to permit desk for reissuing.
|
Telephone call | | | 6/30/2006 | | DONE |
|
|
|
tlk to secretary for dan nemichele ###-#### that 2nd review is ready to be picked up no fee
|
Plan resubmittals received | | | 6/16/2006 | | |
|
|
|
|
Issue and Print Permit | | | 4/13/2006 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 3/22/2006 | | 4/12/2006 | | DONE |
|
|
|
|
Sprinkler Plan Check | 3/22/2006 | | 4/12/2006 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/12/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/12/2006 | | 4/12/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 4/12/2006 | | DONE |
|
|
|
|
Telephone call | | | 4/12/2006 | | DONE |
|
|
|
tlk to receptionist that permit and fees are ready to be picked up - ###-####
|
Application received | | | 3/22/2006 | | |
|
|
|
|