Permit NumberFIR06-00200
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 1549 N CORMORANT PL
Project NameSPR OH HOLBROOK BLDG SHELL
Customer Number 
ePlanReview 
Description
HOLBROOK BUILDING (SHELL) - To install an OH-2 gridded shell fire sprinkler system in a new 15,500-ft/2, one story, steel and wood framed retail and office shell building. This building is fully fire sprinklered. The sprinklers are used for area increase. This is a shell building only and must be finished prior to any tenant occupancy use. No occupancy is allowed under this permit. Separate tenant improvement permits are required to finish this building for occupancy. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The underground fire service supply was permitted under FIR06-00120 (currently unfinished). This permit is attached to building permit: BLD05-02746.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/21/20066/22/20066/22/2006APASS
DetailsTroy Cobbley
Permit finaled.
INSP-Sprinkler Rough-in/Hydro6/20/20066/21/20066/21/2006APART
DetailsTroy Cobbley
Above ground hydro test passed but the forward flush failed.
INSP-Sprinkler Rough-in/Hydro6/20/20066/20/20066/20/2006PCANC
DetailsTroy Cobbley
Wrong permit number called in
INSP-Sprinkler Rough-in/Hydro6/9/20066/12/20066/12/2006APASS
DetailsTroy Cobbley
sprinkler heads added at the beam obstructions..
INSP-Sprinkler Rough-in/Hydro6/5/20066/5/20066/5/2006PFAIL
DetailsTroy Cobbley
See city approved plans for locations where the upright sprinkler heads are being blocked by steel beams. Additional heads will be required. This inspection was for the overhead shell system piping only and did not include the riser or tenant improvement spaces.
Issue and Print Permit  4/19/2006 DONE
Override - Parcel Holds  4/14/2006  
Permit Ready to Issue  4/14/2006 DONE
Telephone call  4/14/2006  
called ###-#### and left message for Randy w/Alicia permit is ready
PLANS/APPL TAKEN TO FRONT DESK  4/14/2006 DONE
Per Bill A. do not issue until plan mod. approved for bld05-02752. Holbrook building shell, Light Syles of Boise TI, and Mortgage Company fire plans all attached. Bill called Debest to tell them permit not ready. Will watch for issuance of plan mod.
Plan assigned to (Bill)3/22/2006 4/13/2006 DONE
Sprinkler Plan Check3/22/2006 4/13/2006 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  4/13/2006 DONE
Override - Parcel Holds  4/13/2006  
FIR permit not directly related to parcel tag 4-13-06 eus
Inspection Record Card- Fire4/13/2006 4/13/2006 DONE
FIR permit not directly related to parcel tag 4-13-06 eus
Application received  3/22/2006