INSP-Final Inspection | 9/13/2006 | 9/15/2006 | 9/15/2006 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Sprinkler Rough-in/Hydro | 8/28/2006 | 8/29/2006 | 8/29/2006 | A | PASS |
Troy Cobbley
|
|
|
The remaining piping on the first floor is ok to cover. Two additional upright sprinkler heads are required as discussed due to duct blockage. Their placement will be verified at the final.
|
INSP-Sprinkler Rough-in/Hydro | 8/24/2006 | 8/25/2006 | 8/25/2006 | P | PART |
Troy Cobbley
|
|
|
The second floor sprinkler piping is ok to cover.
|
INSP-Sprinkler Rough-in/Hydro | 7/24/2006 | 7/24/2006 | 7/24/2006 | P | PASS |
Troy Cobbley
|
|
|
Hydro test of the FDC passed.
|
INSP-Final Inspection | 7/20/2006 | 7/21/2006 | 7/21/2006 | A | FAIL |
Troy Cobbley
|
|
|
Still need to hydro test the FDC and connect/test the alarms. Forward flush passed. The rough-in for the south tenant failed due to numerous obstructions to the upright sprinkler heads by duct work.
|
INSP-Sprinkler Rough-in/Hydro | 7/20/2006 | 7/21/2006 | 7/21/2006 | A | PASS |
Troy Cobbley
|
|
|
Above ground hydro test passed. Still need to hydro the remote FDC.
|
INSP-Supply line flush | 6/28/2006 | 6/29/2006 | 6/29/2006 | P | PASS |
Troy Cobbley
|
|
|
underground supply line flushed passed
|
INSP-Sprinkler Rough-in/Hydro | 6/14/2006 | 6/15/2006 | 6/15/2006 | P | PASS |
Troy Cobbley
|
|
|
Piping understairs, above restroom and entry lobby ok to cover.
|
INSP-Sprinkler Rough-in/Hydro | 6/14/2006 | 6/16/2006 | 6/14/2006 | P | CANC |
Troy Cobbley
|
|
|
Contact is Jeff Chaney; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|
INSP-Sprinkler Rough-in/Hydro | 6/12/2006 | 6/12/2006 | 6/13/2006 | P | PASS |
Troy Cobbley
|
|
|
200lb Hydro Test Passed
|
Plan assigned to (Bill) | 3/28/2006 | | 5/1/2006 | | DONE |
|
|
|
|
Sprinkler Plan Check | 4/10/2006 | | 5/1/2006 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/1/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/1/2006 | | 5/1/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 5/1/2006 | | DONE |
|
|
|
|
Telephone call | | | 5/1/2006 | | |
|
|
|
called ###-#### and left message for Randy Bowron that permit is ready and fee
|
CHANGE STATUS TO (ISS) | | | 5/1/2006 | | DONE |
|
|
|
|
(F) Reprint permit | | | 5/1/2006 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 4/27/2006 | 4/27/2006 | 4/27/2006 | P | PASS |
Troy Cobbley
|
|
|
The remaining portion of the underground is ok to cover
|
Plan resubmittals received | | | 4/10/2006 | | DONE |
Bill Alexander
|
|
|
|
Telephone call | | | 4/5/2006 | | DONE |
|
|
|
4/5/2006 - SLR to Gordon Goldsmith - I spoke with Randy this morning regarding your email below. After a little questioning from me as to the real reason for their problem, I suggested several alternative methods of providing the valving. As he started to look at their design closer, he acknowledged that he thought he could see a solution and he will go back and discuss it with his designer. My guess is that they will find a way to put the valve in. If they can't, I told him he would need to bring in the sprinkler piping plans, including floor plans and elevations and sections, which clear show what it is that prevents any control valve from being installed, and then we would have a basis for a discussion. He agreed to do that if necessary.
So you're off the hook for now, Gordon.
Sam
>>> GORDON GOLDSMITH 4/4/2006 5:45 PM >>>
Sam, I had a lengthy discussion with Randy at DeBest. He is asking for the FM to approve the omission of the second floor control valve, (BCC Chapter 7- 903.1.5), because of lack of space and other issues. The core/shell BLD 05-01262 FIR 06-00161 approved by Bill A. and FIR 06-00218, 219, and 220 that were disapproved. Address is 1897 Wildwood the Ted Mason Building. Randy was lobbying hard for my approval, he assured me that if there was an alternative he would not be calling the FM making this request. Obviously I am stepping in this position w/o any history or information regarding this issue. I have deferred him back to you regarding his building construction issue. If after talking to Randy you could advice Chief Hanneman or myself, an informed decision could be made. Thanks Sam for you help!
|
Issue and Print Permit | | | 3/31/2006 | | DONE |
|
|
|
|
Sprinkler Plan Check | 3/9/2006 | | 3/30/2006 | | FAIL |
Bill Alexander
|
|
|
Re-Submittals Of The Following Items Are Required:
1. Floor control assemblies are required for any building 2 or more levels in height. Revise and resubmit. (BMC 7-01-55 IFC 903.1.5)
|
Miscellaneous action | | | 3/30/2006 | | DONE |
|
|
|
Took permit documents to permit desk for returning.
|
Telephone call | | | 3/30/2006 | | DONE |
|
|
|
called ###-#### and left message for Randy with Alicia permit failed needs picked up
|
Application received | | | 3/28/2006 | | |
|
|
|
|
Case Summary | | | 3/28/2006 | | |
|
|
|
|