Permit Information
Permit NumberFIR06-00219
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 1891 N WILDWOOD AVE
Project NameSPR THE SIGN CENTER
Customer Number 
ePlanReview 
Description
THE SIGN CENTER - STEELWOOD FLEX CONDOS - BLDG 3 - UNITS 20/21-1ST FLR * This building is fire sprinklered for story increase and for fire flow. To modify a shell system by adding and relocating fire sprinklers for a new 2,594-ft/2 sign fabrication tenant facility with some office and storage on the first floor of existing vacant shell building. Units 20 and 21 will be merged to act as one condo unit but there will be separate tenants on each floor. The shell was constructed as a one story building under permit BLD05-01262. Fire sprinkler work is related to the installation of new interior walls, new accessible restrooms and some suspended ceiling work. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The shell fire sprinklers were permitted under FIR06-00161. This permit is attached to BLD05-03243.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/5/200612/5/200612/6/2006PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro7/25/20067/26/20067/26/2006PCANC
DetailsTroy Cobbley
Wrong inspection type called in. It should have been for a final.
INSP-Final Inspection7/26/20067/26/20067/26/2006PPART
DetailsTroy Cobbley
A temporary occupancy is approved with dave hanniman's permission until the south tenant space has been completed. This permit is ok to final when that happens.
INSP-Final Inspection7/14/20067/17/20067/17/2006ACANC
DetailsTroy Cobbley
Contact: Chris; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
FIR-Aging Inspection7/14/20067/14/20067/14/2006 NR
DetailsTroy Cobbley
work is in progress
Sprinkler Plan Check4/10/2006 5/1/2006 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  5/1/2006 DONE
Permit Ready to Issue  5/1/2006 DONE
Inspection Record Card- Fire5/1/2006 5/1/2006 DONE
Telephone call  5/1/2006 DONE
called ###-#### and left message for Randy Bowron that permit is ready and fee
CHANGE STATUS TO (ISS)  5/1/2006 DONE
(F) Reprint permit  5/1/2006 DONE
Plan assigned to (Bill)3/28/2006 5/1/2006 DONE
Plan resubmittals received  4/10/2006 DONE
DetailsBill Alexander
Telephone call  4/5/2006 DONE
4/5/2006 - SLR to Gordon Goldsmith - I spoke with Randy this morning regarding your email below. After a little questioning from me as to the real reason for their problem, I suggested several alternative methods of providing the valving. As he started to look at their design closer, he acknowledged that he thought he could see a solution and he will go back and discuss it with his designer. My guess is that they will find a way to put the valve in. If they can't, I told him he would need to bring in the sprinkler piping plans, including floor plans and elevations and sections, which clear show what it is that prevents any control valve from being installed, and then we would have a basis for a discussion. He agreed to do that if necessary.
So you're off the hook for now, Gordon.
Sam

>>> GORDON GOLDSMITH 4/4/2006 5:45 PM >>>
Sam, I had a lengthy discussion with Randy at DeBest. He is asking for the FM to approve the omission of the second floor control valve, (BCC Chapter 7- 903.1.5), because of lack of space and other issues. The core/shell BLD 05-01262 FIR 06-00161 approved by Bill A. and FIR 06-00218, 219, and 220 that were disapproved. Address is 1897 Wildwood the Ted Mason Building. Randy was lobbying hard for my approval, he assured me that if there was an alternative he would not be calling the FM making this request. Obviously I am stepping in this position w/o any history or information regarding this issue. I have deferred him back to you regarding his building construction issue. If after talking to Randy you could advice Chief Hanneman or myself, an informed decision could be made. Thanks Sam for you help!
Issue and Print Permit  3/31/2006 DONE
Sprinkler Plan Check3/9/2006 3/30/2006 FAIL
DetailsBill Alexander
Re-Submittals Of The Following Items Are Required:
1. Floor control assemblies are required for any building 2 or more levels in height. Revise and resubmit. (BMC 7-01-55 IFC 903.1.5)
Miscellaneous action  3/30/2006 DONE
Took failed documents to permit desk for returning and corrections.
Telephone call  3/30/2006 DONE
called ###-#### and left message for Randy with Alicia permit failed needs picked up
Case Summary  3/28/2006 DONE
Application received  3/28/2006