INSP-Final Inspection | 5/5/2006 | 5/5/2006 | 5/5/2006 | P | PASS |
Troy Cobbley
|
|
|
Fire sprinklers finaled
|
INSP-Sprinkler Rough-in/Hydro | 5/4/2006 | 5/4/2006 | 5/4/2006 | P | PASS |
Troy Cobbley
|
|
|
Permit is ok to final when the fire alarm permit is finaled.
|
INSP-Sprinkler Rough-in/Hydro | 5/3/2006 | 5/4/2006 | 5/4/2006 | A | CANC |
Troy Cobbley
|
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles reshedule for pm
|
INSP-Sprinkler Rough-in/Hydro | 5/3/2006 | 5/3/2006 | 5/3/2006 | P | PASS |
Troy Cobbley
|
|
|
Above ground hydro test passed. I performed a partial rough-in inspection. The EFSR heads were too close to the truss webbing. Some EQ bracing still needed to be installed.
|
INSP-Sprinkler Rough-in/Hydro | 5/3/2006 | 5/3/2006 | 5/3/2006 | P | CANC |
Troy Cobbley
|
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles wants to rescheduled for 5/4/2006
|
Plan resubmittals received | | | 4/27/2006 | | DONE |
|
|
|
|
Sprinkler Plan Check | 4/27/2006 | | 4/27/2006 | | PASS |
Bill Alexander
|
|
|
|
Miscellaneous action | | | 4/27/2006 | | DONE |
|
|
|
Took Modified plans, documents to permit desk for releasing. No fee-2nd review.
|
Issue and Print Permit | | | 4/24/2006 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 3/29/2006 | | 4/21/2006 | | DONE |
|
|
|
|
Sprinkler Plan Check | 3/29/2006 | | 4/21/2006 | | PART |
Bill Alexander
|
|
|
Re-Submittals Of The Following Items Are Required:
1. When retroactive installation work and/or backflow prevention devices are to be installed on existing systems, a thorough hydraulic analysis, including revised hydraulic calculations, new fire flow data, and all necessary system modifications to accommodate the additional friction loss, shall be completed as a part of the installation on any existing system. (NFPA 13-8.16.4.6.2, 11.2.2.8.2, 14.1.3[30], BMC 7-01-50 IFC 901.2, IFC 105.4.2)
2. Backflow prevention shall be provided with required forward flow components/provisions in accordance with requirements addressed in NFPA 13-8.16.4.6.1*.
3. The working plan submittal shall include the manufacturer's installation instructions for any specially listed equipment, including descriptions, applications, and limitations for any (Sidewalls) sprinklers, devices, piping, or fittings. (NFPA 13-14.1.4)
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/21/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/21/2006 | | 4/21/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 4/21/2006 | | DONE |
|
|
|
|
Telephone call | | | 4/21/2006 | | DONE |
|
|
|
lt vm with greg patrick ###-#### that permit and fees are ready to be picked up
|
Miscellaneous action | | | 4/19/2006 | | DONE |
|
|
|
Approved Early Start requrest for installation of rough-in piping only, with my comment to refer to issued building plan review comments relative to sprinklers. Request states the existng system is to remain in service and will not be modified and no connection of new system piping to exisitng riser until plans have been approved and issued.
|
Application received | | | 3/29/2006 | | |
|
|
|
|
Case Summary | | | 3/29/2006 | | DONE |
|
|
|
|