INSP-Final Inspection | 5/10/2006 | 5/10/2006 | 5/11/2006 | P | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
INSP-Alarm Testing | 5/9/2006 | 5/9/2006 | 5/10/2006 | P | PASS |
Forrest France
|
|
|
Fire alarm passed final inspection, required corrections have been made.
|
INSP-Alarm Testing | 5/4/2006 | 5/5/2006 | 5/5/2006 | A | FAIL |
Forrest France
|
|
|
Two HVAC units not functional to enable testing, need to provide an updated map at the panel showing new monitor points, provide as builts reflecting field changes for EOL and device addresses, provide date on NAC batteries. Two pull stations, one duct detector and a/v notification devices tested okay.
|
INSP-Final Inspection | 5/4/2006 | 5/4/2006 | 5/4/2006 | A | NR |
Forrest France
|
|
|
Panel must be free of ground fault condition prior to final alarm testing.
|
INSP-Alarm Testing | 5/3/2006 | 5/3/2006 | 5/4/2006 | P | CANC |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 5/3/2006 at 9:01:50 AM. Contact: ###-####.
|
Issue and Print Permit | | | 4/27/2006 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 4/3/2006 | | 4/26/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 4/26/2006 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/26/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/26/2006 | | 4/26/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 4/26/2006 | | DONE |
|
|
|
|
Telephone call | | | 4/26/2006 | | DONE |
|
|
|
tlk to john lopez ###-#### that permit and fees are ready to be picked up
|
Plan resubmittals received | | | 4/18/2006 | | |
|
|
|
|
Alarm Plan Check | | | 4/14/2006 | | FAIL |
|
|
|
Resubmittal required. the builsind has what appears to be a "manual" fire alarm system. Pull stations are required at all "exits" and notification required in the egress from the TI space.
|
Telephone call | | | 4/13/2006 | | DONE |
|
|
|
Left a message for John Lopez to call me. The submittal has insufficient information regarding the existing system. I want to schedule a walk through before processing this permit and FIR06-00246.
|
Application received | | | 4/3/2006 | | |
|
|
|
|