INSP-Alarm Testing | 7/12/2006 | 7/13/2006 | 7/13/2006 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
DOC - Permit Finaled | | | 7/13/2006 | | PASS |
|
|
|
|
INSP-Alarm Testing | 7/10/2006 | 7/10/2006 | 7/10/2006 | P | FAIL |
Troy Cobbley
|
|
|
No test performed due to ehen the manual pull station in the basement was pulled not a/v's went off. The pull station that was tested did not corrispond with the assigned address on the plans. Also the a/v in the kitchen needs to be relocated as discussed due to blockage by duct work. All other a/v's appear to be located correctly. No other testing was done.
|
Inspection Record Card- Fire | 4/27/2006 | | 4/27/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 4/27/2006 | | DONE |
|
|
|
|
Issue and Print Permit | | | 4/27/2006 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 4/3/2006 | | 4/26/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 4/26/2006 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/26/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 4/18/2006 | | |
|
|
|
|
Alarm Plan Check | | | 4/14/2006 | | FAIL |
|
|
|
Resubmittal required. the builsind has what appears to be a "manual" fire alarm system. Pull stations are required at all "exits" and notification required in the egress from the TI space.
|
Telephone call | | | 4/13/2006 | | DONE |
|
|
|
Left a message for John Lopez to call me. The submittal has insufficient information regarding the existing system. I want to schedule a walk through before processing this permit and FIR06-00245.
|
Application received | | | 4/3/2006 | | |
|
|
|
|
Case Summary | | | 4/3/2006 | | DONE |
|
|
|
|