INSP-Final Inspection | 6/14/2007 | 6/15/2007 | 6/15/2007 | A | PASS |
Forrest France
|
|
|
Fire supply line permit finaled.
|
INSP-Sprinkler Rough-in | 11/2/2006 | 11/3/2006 | 11/3/2006 | A | DEFR |
Forrest France
|
|
|
Wrong permit number called in, was intended for the overhead permit work.
|
INSP-Sprinkler Rough-in/Hydro | 10/16/2006 | 10/16/2006 | 10/16/2006 | P | PART |
Forrest France
|
|
|
UG fire supply line is okay for cover, UG also passed hydrostatic test, noted marked locations for the FDC and WPI appear too low above finish grade.
|
INSP-Sprinkler Rough-in | 10/16/2006 | 10/16/2006 | 10/16/2006 | P | CANC |
Forrest France
|
|
|
bruce - note: call 1/.2 hr prior to going out 5th floor; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
Issue and Print Permit | | | 5/19/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 5/18/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/18/2006 | | 5/18/2006 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 4/11/2006 | | 5/18/2006 | | DONE |
|
|
|
|
Sprinkler Plan Check | 5/12/2006 | | 5/18/2006 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/18/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 5/12/2006 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 4/13/2006 | | 4/17/2006 | | FAIL |
Bill Alexander
|
|
|
Re-Submittals Of The Following Items Are Required:
1. Plan is incomplete and/or unreadable. Information is lacking and clarified, (correct) dimensioned plan/s is required. Information shall be all encompassing with enough detail to clarify the full scope of the work involved with the permit requested. "U.G. Permit" needs clarified in order to address minimum installation code.
a. Provide clarification of all piping installing, how all is entering/leaving the facility which shall include but may not be limited too:
1. Elevations,
2. Thrust protection,
3. Clearance,
4. Type and size of all pipe installing,
5. Identify all fittings, valves, transition, etc.
6. Clarified location of P.I.V.
7. Elevation of P.I.V addressing limit required per NFPA 13.
8. Provide elevation of F.D.C. addressing limits allowed per the IFC and NFPA 13 and 14.
2. Provide clarification of symbols, (differentiate between a hydrant and fire department connections).
3. Provide data submittals on the FDC. Address whether the FDC is a combination FDC/Standpipe, and include the correct identification of the same incorporating on the plan.
4. Provide clarification that hydrant/s are not connected to the fire sprinkler service supply line installing, meeting requirements of the BMC-IFC.
5. Include depth of bury of all pipe installing, measured from the top to finish grade.
6. This facility will most likely require a standpipe required during construction. Will the FDC installing be connected to the standpipe required under IFC 1413? If so, address this on the plans.
NOTE: Temporary standpipes in buildings being constructed will require prior permit approval before installation or any work for the same.
|
Telephone call | | | 4/17/2006 | | DONE |
|
|
|
tlk to john warnick ###-#### that permit failed and needs to be picked up
|
Case Summary | | | 4/11/2006 | | DONE |
|
|
|
|
Application received | | | 4/11/2006 | | |
|
|
|
|
Inspection Record Card- Fire | 5/18/2006 | | | | |
|
|
|
|