INSP-Final Inspection | 12/19/2006 | 12/20/2006 | 12/20/2006 | A | PASS |
Forrest France
|
|
|
Final fire alarm test is satisfactory, permit finaled.
|
INSP-Final Inspection | 12/12/2006 | 12/15/2006 | 12/15/2006 | P | FAIL |
Forrest France
|
|
|
The flow switch at the riser functions intermittently, SD at the panel tested okay, final pending correct operation of the waterflow switch.
|
INSP-Final Inspection | 12/6/2006 | 12/8/2006 | 12/8/2006 | P | FAIL |
Forrest France
|
|
|
Intermittent operation of the flow switch must be repaired prior to alarm final, need to provide map at the panel as discussed, SD at the FACP to be tested at next inspection, all other items tested satisfactory.
|
(F) Reprint permit | | | 8/8/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/8/2006 | | 8/8/2006 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 8/8/2006 | | |
|
|
|
|
Alarm Plan Check | 7/31/2006 | | 7/31/2006 | | PASS |
|
|
|
Plan Modification approved as is, without comments. Relocated location of FACP. No fee.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/31/2006 | | DONE |
|
|
|
No fee.
|
Permit Ready to Issue | | | 7/31/2006 | | DONE |
|
|
|
|
Telephone call | | | 7/31/2006 | | DONE |
|
|
|
left vm@###-####/told permit was ready, permit#, project name & address, and no fees
|
Plan resubmittals received | | | 7/11/2006 | | |
|
|
|
|
Case Summary | | | 7/11/2006 | | DONE |
|
|
|
|
Issue and Print Permit | | | 5/5/2006 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 4/13/2006 | | 5/2/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 5/2/2006 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/2/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 5/2/2006 | | DONE |
|
|
|
|
Telephone call | | | 5/2/2006 | | DONE |
|
|
|
left mess that permit is ready
|
Inspection Record Card- Fire | 5/2/2006 | | 5/2/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 4/26/2006 | | |
|
|
|
|
Case Summary | | | 4/26/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 4/20/2006 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Rob Ahten.
|
Application received | | | 4/13/2006 | | |
|
|
|
|
Case Summary | | | 4/13/2006 | | |
|
|
|
|