INSP-Final Inspection | 7/26/2006 | 7/27/2006 | 7/27/2006 | A | PASS |
Forrest France
|
|
|
Required corrections have been verified, one non functional RTS for duct detector 12 has been repaired, fire alarm permit finaled.
|
INSP-Final Inspection | 7/24/2006 | 7/25/2006 | 7/25/2006 | A | FAIL |
Forrest France
|
|
|
Descriptors for pull stations do not match point descriptions on the plan, AC power loss is incorrectly identified as NAC trouble, the duct detectors activate a general alarm condition. Need to provide list of signals recieved by remote monitoring of test activity today at next inspection. Notification devices tested okay.
|
INSP-Final Inspection | 7/24/2006 | 7/24/2006 | 7/24/2006 | P | CANC |
Troy Cobbley
|
|
|
bill ###-####
|
Plan assigned to (Mary) | 4/13/2006 | | 5/16/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 5/16/2006 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/16/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/16/2006 | | 5/16/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 5/16/2006 | | DONE |
|
|
|
|
Telephone call | | | 5/16/2006 | | |
|
|
|
tlk to laura ###-#### that permit and fees are ready to be picked u-
|
Issue and Print Permit | | | 5/16/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 5/10/2006 | | |
|
|
|
|
Alarm Plan Check | | | 4/25/2006 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Corrine McKague.
|
Application received | | | 4/13/2006 | | |
|
|
|
|