Information based on query as of Saturday, August 17, 2024.
Permit Information
Permit NumberFIR06-00281
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 350 N BELLA VIA PL
Project NameSPR SEAN CAFFERTY-HOME
Customer Number 
ePlanReview 
Description
SEAN CAFFERTY - HOME * To install a (modified) life safety NFPA 13D system in a new two story 4955-ft/2, single family dwelling with a 1,392 Basement, 2411-ft/2 Main Level, 1152-ft/2 Upper Level and a 1252-ft/2 attached garage. The modification is the installation of a single row of dry sidewall sprinklers along the common wall attached to the garage and the living space. System will be equipped with an alarm initiating device and an outside alarm. All fire sprinkler work and related, which includes dual use, single service water supply, the system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD05-02327.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/26/200610/27/200610/27/2006PPASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Final Inspection10/25/200610/26/200610/26/2006PPART
DetailsForrest France
Supply line flush completed satisfactory, contractor not ready for final at this time as the riser is not completed and missing some items such as calc. stickers, signs, locks for control valves, head box, etc., still need to perform alarm test.
INSP-Sprinkler Rough-in5/26/20065/30/20065/30/2006APASS
DetailsTroy Cobbley
Corrections as noted on the approved plans have been corrected. Sprinkler piping is ok to cover.
INSP-Sprinkler Rough-in5/23/20065/24/20065/24/2006AFAIL
DetailsForrest France
One head in the basement as circled on approved plans requires vertical restraint, the 5' section of 11/4 pipe as circled on plans exceeds allowable deflection distances, need to provide cold cavity protection above the dining area, one head has been added in the second floor bathroom, some areas as piped do not match routing as shown on stamped plans.
Permit Ready to Issue  5/2/2006 DONE
Inspection Record Card- Fire5/2/2006 5/2/2006 DONE
Telephone call  5/2/2006 DONE
tlk to jon edes ###-#### that permit and fees are ready to be picked up
Inspection Record Card- Fire5/2/2006 5/2/2006 DONE
Issue and Print Permit  5/2/2006 DONE
Plan assigned to (Bill)4/17/2006 5/1/2006 DONE
Sprinkler Plan Check4/17/2006 5/1/2006 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  5/1/2006 DONE
Case Summary  4/17/2006 DONE
Application received  4/17/2006