Permit Information
Permit NumberFIR06-00282
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 1109 W MYRTLE ST Unit: 300
Project NameSPR NYL PIONEER PLZA 300
Customer Number 
ePlanReview 
Description
NEW YORK LIFE - PIONEER PLAZA - STE 300 * This building is fully fire sprinklered for one-hour substitution. To replace all existing Standard Response (114 SSP's & 1 SSU) with Quick Response sprinklers. To relocate 29 positions and add 31 new positions within the remodel a 9,558-ft/2 office tenant which will occupy the entire third floor of an existing building. Fire sprinkler work is related to the (possible) downgrading of construction and extending exit travel distances, new interior walls and some small areas of suspended ceiling work. Some sprinkler demolition work was accomplished under FIR06-00225 by another contractor. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD06-00401.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/19/20065/22/20065/22/2006PPASS
DetailsForrest France
Fire sprinkler passed inspection, permit finaled.
Miscellaneous action  5/19/2006 DONE
Returned corrected plans to permit desk.
Telephone call  5/19/2006  
tlk to receptionist that permit and ready to picked up no fee ###-####
Plan resubmittals received  5/18/2006  
received plan resubmittals
Sprinkler Plan Check5/18/2006 5/18/2006 PASS
DetailsBill Alexander
INSP-Sprinkler Rough-in/Hydro5/16/20065/17/20065/17/2006APART
DetailsForrest France
Inspection was for overhead rough-in cover. The installation matches plans which are currently being resubmitted per contractor. Rough-in as installed is okay pending city plan review approval. Three areas as marked on plans need corrected including overspacing at a corridor intersection, head too close to a wall in SW room, the elevator shaft head needs to be QR.
Issue and Print Permit  5/3/2006  
Plan assigned to (Bill)4/18/2006 5/2/2006 DONE
Sprinkler Plan Check4/18/2006 5/2/2006 PART
DetailsBill Alexander
Re-Submittals Of The Following Items Are Required:
1. Shilo Automatic Sprinklers is not meeting minimum design requirements for the occupancy hazard and system modifications provided, due to several reasons:
a. This AHJ cannot read riser detail for pipe sizing including the backflow device and related friction loss.
b. Cannot determine why the area verifying was chosen since it is not the most remote/demanding.
i. It would appear addressing 11.2.3.3, since the room is outlined for the test is surrounded by walls? If the designer is representing a room design (method), it is unacceptable since no construction information was provided. Please reference 11.2.3.3.3. To utilize the room design method, all rooms (floor) shall be enclosed with walls having a fire-resistance rating equal to the water supply duration indicated in Table 11.2.3.1.1.
ii. To utilize the room design method then information regarding 11.2.3.3.5 should be addressed. Minimum protection of openings for Light hazard - Non-rated automatic or self-closing doors.
iii. Where openings are not protected, calculations shall include the sprinklers in the room plus two sprinklers in the communicating space nearest each such unprotected opening unless the communicating space has only one sprinkler, in which case calculations shall be extended to the operation of that sprinkler. The selection of the room and communicating space sprinklers to be calculated shall be that which produces the greatest hydraulic demand.
Provide a design that can be identified and verified meeting minimum design code addressing one of the following methods, since no other method will apply:
a. 11.2.3.2 Density/Area Method.
b. 11.2.3.3 Room Design Method.

2. The installation and incorporation of mechanical tees involving calculations shall reflect the friction loss for the same, which is normally higher than standard tee fittings.

3. No protection shown in the elevator shaft. Verify this is so. If protection is provided, heads must also be upgraded to Q.R.'s.

4. Stairwell between columns "G" and "F" and "2" and "3," appear to not be included in this permit, even though head count is including it. IFC Fire/Life Safety Inspector verify upgrading of heads to Q.R.'s.
PLANS/APPL TAKEN TO FRONT DESK  5/2/2006 DONE
Inspection Record Card- Fire5/2/2006 5/2/2006 DONE
Permit Ready to Issue  5/2/2006 DONE
Telephone call  5/2/2006 DONE
tlk to debest ###-#### that permit and fees are ready to be picked up
Case Summary  4/18/2006  
Application received  4/18/2006