INSP-Final Inspection | 6/19/2006 | 6/20/2006 | 6/20/2006 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 6/14/2006 | 6/15/2006 | 6/15/2006 | A | FAIL |
Troy Cobbley
|
|
|
Tried to contact Mark twice and I stopped at the bank to see if the manager could let me in but he was not there either. No inspection performed.
|
INSP-Final Inspection | 6/13/2006 | 6/14/2006 | 6/14/2006 | P | CANC |
Troy Cobbley
|
|
|
Canceled at Mark's request. Work was not going to be completed.
|
INSP-Sprinkler Rough-in | 5/5/2006 | 5/8/2006 | 5/8/2006 | A | FAIL |
Troy Cobbley
|
|
|
Per the plans the Server Room is to be Ordinary Hazard. The small room rule has been utilized plus the square footage of the room exceeds the coverage of what two heads could provide at 130sq ft each. The plans also indicate that the new pendants in the other room are to have a maximum spacing of 168 sq. ft. but are actually spaced at 183 sq. ft.. Also one sprig up has been left installed above what is going to be a ceiling. This upright will need to be removed.
|
Issue and Print Permit | | | 4/26/2006 | | DONE |
|
|
|
|
Telephone call | | | 4/25/2006 | | DONE |
|
|
|
tlk to secretary ###-#### that permit and fees are ready to be picked up
|
Plan assigned to (Bill) | 4/19/2006 | | 4/24/2006 | | DONE |
|
|
|
|
Sprinkler Plan Check | 4/19/2006 | | 4/24/2006 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/24/2006 | | DONE |
|
|
|
|
Case Summary | | | 4/24/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/24/2006 | | 4/24/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 4/24/2006 | | |
|
|
|
|
Application received | | | 4/19/2006 | | |
|
|
|
|