Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberFIR06-00296
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 276 N 8TH ST
Project NameSPR COLD STONE CREAMERY
Customer Number 
ePlanReview 
Description
COLD STONE CREAMERY-IDAHO BLDG-1ST FLR * To and new fire sprinkler protection by modifying the existing system for the build-out of a 1,588-ft/2 shell tenant space, created under BLD06-00012, for use as an ice cream shop with seating. Fire sprinkler work is related to the construction of new interior non-bearing walls to create seating, service, work and storage areas and new suspended ceilings. This building is fully sprinklered per 1994 UCBC because it is too tall and has too many stories. The fire sprinkler system work shall comply with IFC 2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD6-00213.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/9/20066/9/20066/9/2006PPASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Final Inspection6/7/20066/8/20066/8/2006AFAIL
DetailsForrest France
The existing building fire sprinkler system is not yet current with an annual inspection, ceiling tile is missing at several locations, some escutcheons are still missing.
INSP-Final Inspection6/1/20066/2/20066/2/2006AFAIL
DetailsForrest France
Ceiling tile at several locations is not installed, missing escutcheons at several areas.
INSP-Final Inspection5/10/20065/12/20065/12/2006APART
DetailsForrest France
Corrections for the overhead rough-in have been completed, installation is good for cover, final pending cooler construction for dry pendents and ceiling tile/escutcheons at the drop ceiling areas.
INSP-Sprinkler Rough-in5/5/20065/8/20065/8/2006APART
DetailsForrest France
Rough-in is good for cover at the restroom and counter soffit hard lid areas only, noted one head is overspaced at the drop ceiling area as marked on approved plans, not all drop ceiling areas are ready for inspection at this time, will require matching response type heads in the same fire area.
INSP-Sprinkler Rough-in5/5/20065/5/20065/7/2006PCANC
DetailsForrest France
No time to complete inspection, to be rescheduled per conversation with contractor.
INSP-Sprinkler Rough-in5/1/20065/2/20065/1/2006PCANC
DetailsForrest France
###-#### Mike\\per Mary can not have insp.
Issue and Print Permit  4/27/2006  
Plan assigned to (Bill)4/21/2006 4/26/2006 DONE
Plan resubmittals received  4/26/2006  
Sprinkler Plan Check4/26/2006 4/26/2006 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  4/26/2006 DONE
Case Summary  4/26/2006 DONE
Inspection Record Card- Fire4/26/2006 4/26/2006 DONE
Permit Ready to Issue  4/26/2006 DONE
Telephone call  4/26/2006 DONE
tlk to bob ###-#### that permit and fees are ready to be picke dup
Sprinkler Plan Check4/21/2006 4/25/2006 FAIL
DetailsBill Alexander
Floor plan is undreadalbe.
Telephone call  4/25/2006 DONE
Called Trent Bice.
Requested:
1. Floor plan that is readable.
2 Head data sheets with the actual heads using identified.
Application received  4/21/2006  
INSP-Sprinkler Rough-in5/3/20065/3/2006