INSP-Final Inspection | 3/16/2010 | 3/17/2010 | 3/17/2010 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
Miscellaneous action | | | 3/12/2010 | | DONE |
|
|
|
Sent email requesting project status.
|
Plan assigned to (Scott) | 7/6/2006 | | 11/1/2006 | | PASS |
|
|
|
11/1/2006 15:59:40 SLR - activity updated through activity FIRA22 from case FIR06-00463.
|
INSP-Sprinkler Rough-in/Hydro | 10/23/2006 | 10/23/2006 | 10/23/2006 | P | PART |
Forrest France
|
|
|
UG hydrostatic test passed.
|
INSP-Sprinkler Rough-in/Hydro | 10/19/2006 | 10/20/2006 | 10/20/2006 | P | FAIL |
Troy Cobbley
|
|
|
Hydro test failed
|
INSP-Supply line flush | 7/31/2006 | 7/31/2006 | 8/1/2006 | P | PART |
Forrest France
|
|
|
UG fire supply line flush performed satisfactory.
|
INSP-Sprinkler Rough-in | 7/13/2006 | 7/14/2006 | 7/14/2006 | A | PART |
Troy Cobbley
|
|
|
Underground sprinkler supply line as shown on the plans is 6". As installed piping is 4". I have allowed the piping to be buried under the condition that Bill Alexander is contacted and the overhead plans are modified to show this change.
|
CHANGE STATUS TO (ISS) | | | 7/7/2006 | | DONE |
|
|
|
|
(F) Reprint permit | | | 7/7/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 7/6/2006 | | DONE |
|
|
|
|
Sprinkler Plan Check | 7/6/2006 | | 7/6/2006 | | PASS |
|
|
|
Plan Modification. Review comments attached to plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/6/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/6/2006 | | DONE |
|
|
|
|
Telephone call | | | 7/6/2006 | | |
|
|
|
spoke to trent@###-####/told permit was ready and no fee
|
Issue and Print Permit | | | 5/4/2006 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 4/26/2006 | | 5/3/2006 | | DONE |
|
|
|
|
Sprinkler Plan Check | 4/26/2006 | | 5/3/2006 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/3/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/3/2006 | | 5/3/2006 | | DONE |
|
|
|
|
Telephone call | | | 5/3/2006 | | DONE |
|
|
|
tlk to trent bice ###-#### that permit and fees are ready to picked up
|
Permit Ready to Issue | | | 5/3/2006 | | DONE |
|
|
|
|
Application received | | | 4/26/2006 | | |
|
|
|
|