INSP-Final Inspection | 6/15/2006 | 6/16/2006 | 6/16/2006 | A | PASS |
Forrest France
|
|
|
Fire sprinkler work is acceptable, one HVAC register to be relocated a min. 1' away from a pendent at the west side-to be verified at life safety final.
|
INSP-Sprinkler Rough-in/Hydro | 6/6/2006 | 6/7/2006 | 6/7/2006 | A | PASS |
Troy Cobbley
|
|
|
Sprinkler rough-in passed. Some of the drops are overspaced by a few inches. These sprinklers are on 15' long drops which once tile is in may be spaced correctly. This will be checked at final.
|
Issue and Print Permit | | | 5/9/2006 | | |
|
|
|
|
Plan assigned to (Bill) | 4/26/2006 | | 5/8/2006 | | DONE |
|
|
|
|
Sprinkler Plan Check | 4/26/2006 | | 5/8/2006 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/8/2006 | | DONE |
|
|
|
|
Case Summary | | | 5/8/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/8/2006 | | 5/8/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/8/2006 | | 5/8/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 5/8/2006 | | DONE |
|
|
|
|
Telephone call | | | 5/8/2006 | | DONE |
|
|
|
tlk to brad bettoncourt ###-#### that permit and fees are ready to be picked up
|
Application received | | | 4/26/2006 | | |
|
|
|
|