INSP-Final Inspection | 6/24/2006 | 6/26/2006 | 6/26/2006 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 6/20/2006 | 6/21/2006 | 6/21/2006 | A | FAIL |
Troy Cobbley
|
|
|
Strobes are mounted too low and candella is wrong. See plans for locations.
|
Issue and Print Permit | | | 5/5/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 5/4/2006 | | PASS |
|
|
|
Approved pending PDS Fire Inspector field verification. No comments written.
|
Plan assigned to (Mary) | 4/28/2006 | | 5/4/2006 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/4/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/4/2006 | | 5/4/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 5/4/2006 | | DONE |
|
|
|
|
Telephone call | | | 5/4/2006 | | |
|
|
|
tlk to charlie bayne ###-#### that permit and fees are ready to be picked up
|
Telephone call | | | 5/3/2006 | | DONE |
|
|
|
Spoke with Charlie Bayne, Simplex-Grinnell. The FACP battery calculation indicates only 10% for additional power. Good practice is 20% and I review all permits to that level. He will check on the calculation and let me know what it means, or resumbit for upgrade of batteries.
|
Plan resubmittals received | | | 5/3/2006 | | DONE |
|
|
|
Received revised battery calculations via fax.
|
Application received | | | 4/28/2006 | | |
|
|
|
|
Case Summary | | | 4/28/2006 | | DONE |
|
|
|
|