INSP-Final Inspection | 11/21/2006 | 11/21/2006 | 11/21/2006 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
Plan assigned to (Bill) | 4/28/2006 | | 10/20/2006 | | PASS |
|
|
|
10/20/2006 09:02:25 SLR - activity updated through activity FIRA22 from case FIR06-00786.
|
INSP-Sprinkler Rough-in | 9/27/2006 | 9/28/2006 | 9/28/2006 | A | FAIL |
Forrest France
|
|
|
Deflectors must be within 1" to 6" of the bottom of the joist for obstructed combustible construction, see fire code review notes and general notes on plan.
|
Sprinkler Plan Check | 5/1/2006 | | 5/1/2006 | | PASS |
|
|
|
Attached review comments to plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/1/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 5/1/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/1/2006 | | 5/1/2006 | | DONE |
|
|
|
|
Telephone call | | | 5/1/2006 | | DONE |
|
|
|
Spoke with Julie and told her that permit is ready & fees @10:25am 5/1/06 BAS
|
Issue and Print Permit | | | 5/1/2006 | | DONE |
|
|
|
|
Application received | | | 4/28/2006 | | |
|
|
|
|