INSP-Final Inspection | 9/22/2006 | 9/27/2006 | 9/28/2006 | P | PASS |
Forrest France
|
|
|
Fire sprinkler final inspection passed, permit finaled.
|
INSP-Sprinkler Rough-in/Hydro | 9/11/2006 | 9/12/2006 | 9/12/2006 | A | PART |
Forrest France
|
|
|
Re-test of hydrostatic for the underfloor system passed.
|
INSP-Sprinkler Rough-in/Hydro | 9/5/2006 | 9/8/2006 | 9/8/2006 | A | FAIL |
Troy Cobbley
|
|
|
Hydro test failed. Guage appeared to have lost 2-3 psi from 10:15am to 12:15pm.
|
INSP-Sprinkler Rough-in/Hydro | 8/16/2006 | 8/17/2006 | 8/17/2006 | A | PART |
Forrest France
|
|
|
Rough-in for the west underfloor area and OH for the 1st and 2nd levels is acceptable, Hydrostatic test for a portion of these systems at the two 4" main trees and one 3" passed.
|
Plan resubmittals received | | | 7/24/2006 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 7/21/2006 | | 7/24/2006 | | PASS |
Bill Alexander
|
|
|
|
Plan assigned to (Bill) | 5/23/2006 | | 6/24/2006 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 5/23/2006 | | 5/25/2006 | | FAIL |
Bill Alexander
|
|
|
Re-Submittals Of The Following Items Are Required:
1. Section view "A", FP.4.1 shows the cleanroom level pendant heads are incorporating Flexhead® system. It is also noted that all armover, drops (including the Flexhead® piping) is 1¼"?
a. Please provide data submittals addressing these Flexhead® listed units and include identification relating to the lengths incorporating on the project.
b. Reverify and revise calculation addressing the correct (sized) and listed friction loss information for those lengths installing, and resubmit.
2. Hydraulic Calculation "Raised Floor" and "Cleanroom Ceiling" plans conflict or do not correlate. Not all notes on the plans and calculations are found. Basically starting from Node #1 through #4. Raised floor base of riser starts at node #2 and Cleanroom starts at #5? Nodes 5 and 6 calcs conflict with FP.6.0 with the same? Cannot determine if these areas are piped off the same system, since the nodes do not correlate. If separate riser, then identify each separately with each area protecting. If the same then correlate the nodes so they do not conflict. Please reverify and clarify your design and calculations so they correlate, etc.
3. Provide plan clarification with correct piping for draining requirements meeting NFPA 13-8.15.2.5 on the under-floor.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/25/2006 | | DONE |
Bill Alexander
|
|
|
|
Permit Ready to Issue | | | 5/25/2006 | | DONE |
|
|
|
per Bill ok to issue with corrections
|
Issue and Print Permit | | | 5/25/2006 | | DONE |
|
|
|
|
Application received | | | 5/9/2006 | | DONE |
|
|
|
This permit was created on the web by Paul Marcolina
|