Permit Information
Permit NumberFIR06-00351
StatusVoid/No Violation
Name DEBEST FIRE PROTECTION
Site Address 101 N 10TH ST
Project NameSPR OH GEM NOBLE BLDG
Customer Number 
ePlanReview 
Description
(GEM & NOBLE BUILDING RENOVATION) To install a complete wet pipe, Light and OH-2 Occupancy fire sprinkler system in an existing 40'-0" high, (full) basement and 2 story 34,300-ft/2 historic building. Building area is: 11,400-ft/2 basement, 11,400-ft/2 1st story, 11,500-ft/2 2nd story. Building construction work involved with this facility is seismic upgrade, an interior 1-hr stairway, 1-hr corridors, an elevator, 1-hr shafts, new skylights and nine (9) dwelling units on the 2nd floor. Future permits are required for each tenant space to establish occupancy. A (building) demolition permit was issued earlier under BLD04-01307, which was voided 03/08/2005. This building will be fire sprinklered for building area and story increase. It is also being used to allow reduced exit separation on the 2nd story and in the basement, to allow a 27'-0" dead end corridor on the 2nd story, and to allow the common path of egress travel for some dwelling units on the 2nd story to exceed 75'-0" in length. The underground is not included in this permit, but was permitted separately under FIR06-00226. The cavity and 2nd floor is designed for Light Hazard Occupancies per NFPA13-1-4.7.1, Table 12.1.10.1.1, with the 2nd floor modified for NFPA 13-11.2.3.5.1* Residential Sprinklers. The basement and 1st floor are being designed for Ordinary Group 2 occupancy. All portions of the fire protection system design and installation shall comply with the IFC 2000, the attached review comments/conditions and "red lined" stamped plans, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD04-01154.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Sprinkler Rough-in/Hydro1/8/20091/8/20091/8/2009PPART
DetailsForrest France
UG hydrostatic test completed acceptable.
INSP-Conference12/13/200812/15/200812/15/2008ADONE
DetailsForrest France
Regarding portions of permit work both complete and incompleted to date.
Case Summary  3/11/2008 DONE
INSP-Sprinkler Rough-in/Hydro10/19/200610/19/200610/19/2006PFAIL
DetailsForrest France
Need approved plans on site for the TI work prior to inspection for cover or rough-in approval.
INSP-Sprinkler Rough-in/Hydro10/17/200610/19/200610/19/2006ANR
DetailsForrest France
Work is not yet completed for inspection, to be rescheduled for the afternoon.
INSP-Sprinkler Rough-in/Hydro10/13/200610/17/200610/17/2006PCANC
DetailsForrest France
Cover Contact: Jeff; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
Inspection Record Card- Fire5/17/2006 5/17/2006 DONE
Permit Ready to Issue  5/17/2006 DONE
Telephone call  5/17/2006 DONE
Left message for Matthew that permit is ready & fees///5/17/06 @ 9:03am BAS
Issue and Print Permit  5/17/2006 DONE
Plan assigned to (Bill)5/11/2006 5/16/2006 DONE
Sprinkler Plan Check5/11/2006 5/16/2006 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  5/16/2006 DONE
Application received  5/11/2006