INSP-Final Inspection | 3/26/2008 | 3/26/2008 | 3/26/2008 | A | PASS |
Forrest France
|
|
|
Noted corrections are complete, fire sprinkler permit finaled.
|
INSP-Final Inspection | 3/20/2008 | 3/21/2008 | 3/21/2008 | A | FAIL |
Forrest France
|
|
|
Missing ceilings at some locations, need missing escutcheons installed, noted sprinkler head adjacent to the elevator equipment panel must be located within 2' of the heat detector for shunt trip per state elevator requirements.
|
INSP-Final Inspection | 3/18/2008 | 3/18/2008 | 3/18/2008 | P | DEFR |
Forrest France
|
|
|
Wrong permit number requested for inspection.
|
INSP-Final Inspection | 3/13/2008 | 3/14/2008 | 3/14/2008 | A | PART |
Forrest France
|
|
|
Noted this is the wrong permit number requested for inspection-apparently intended for overhead work for the phase two building. Completed sprinkler monitoring testing for flows, tampers and floor control valves, noted one painted head at the first floor entryway, no other areas inspected at this time.
|
INSP-Final Inspection | 2/12/2008 | 2/12/2008 | 2/13/2008 | P | PART |
Forrest France
|
|
|
1st floor walkthrough of the apartment units only -noted 401's have been added at various locations to avoid light fixture obstructions, painted heads indicated at the previous visit have been replaced as necessary.
|
INSP-Final Inspection | 1/30/2008 | 1/31/2008 | 1/31/2008 | A | PART |
Forrest France
|
|
|
Preliminary walkthrough of the 1st and 5th floor units only, noted painted heads at some locations will not be accepted-heads cannot be cleaned but must be replaced due to paint at the seat or element-see units 102 and 505 for typical examples, also noted final head locations cannot be approved at this time due to missing lights and fixtures not yet installed for verification of proper clearances from obstructions.
|
INSP-Final Inspection | 1/15/2008 | 1/16/2008 | 1/16/2008 | A | CANC |
Forrest France
|
|
|
bruce Note: 2, 3, and 4 Phone #: ###-####
|
INSP-Sprinkler Rough-in | 1/14/2008 | 1/15/2008 | 1/15/2008 | A | PART |
Forrest France
|
|
|
Corrections noted at the previous inspection are complete, final pending ceiling tile and escutcheons, will also need plans at next inspection for final review.
|
INSP-Final Inspection | 1/10/2008 | 1/11/2008 | 1/11/2008 | A | FAIL |
Forrest France
|
|
|
Coverage is obstructed by structural columns at five locations.
|
Case Summary | | | 7/20/2007 | | |
|
|
|
|
INSP-Final Inspection | 5/1/2007 | 5/1/2007 | 5/1/2007 | | PART |
|
|
|
Approved for TOC. Ceiling and heating provisions not installed in bsmt parking area; sprinkler installation not completed in Phase two bsmt parking area.
|
FIR-Aging Inspection | 2/20/2007 | 2/20/2007 | 2/23/2007 | | DONE |
Forrest France
|
|
|
Project is under construction, work in progress.
|
Issue and Print Permit | | | 5/19/2006 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/18/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/18/2006 | | 5/18/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 5/18/2006 | | |
|
|
|
|
Plan assigned to (Bill) | 5/12/2006 | | 5/18/2006 | | DONE |
|
|
|
|
Sprinkler Plan Check | 5/12/2006 | | 5/17/2006 | | PART |
Bill Alexander
|
|
|
Re-Submittals Of The Following Items Are Required:
1. Provide a valid and current water supply certificate from the water purveyor. (BMC 7-01-50 IFC 901.2, IFC 105.4.2)
2. Provide hydraulic verification of meeting NFPA 13-14.4.4.2*. (BMC 7-01-50 IFC 901.2, IFC 105.4.2, NFPA 13-14.4.4.2)
3. Provide installation (includes piping information, elevations, fittings, etc.) on the "remote" piped FDC. (BMC 7-01-50 IFC 901.2, IFC 105.4.2)
4. Plan riser detail appears to have a premanufactured riser with flow switch, test-n-drain, etc. If this is the case, provided data submittals for verification.
5. Provide details and clarification through resubmittals on how the system will be protected meeting requirements of NFPA 13-7.6.1.3.2 and 8.15.3.1 minimum.
6. Sprinkler protection is not shown in the bottom of the elevator shafts (pits), which will be required, due to non uniform maintenance (hydraulic fluids) or the accumulation of combustible in the pits over time, etc. Temperature rating of sprinklers in elevator machine rooms and pits shall meet elevator shunt trip requirements per NFPA 72 for operation. (BMC 7-01-50 IFC 901.2, IFC 105.4.2, NFPA 13-8.14.5.1, A.8.14.5.1)
|
Application received | | | 5/12/2006 | | |
|
|
|
|
Case Summary | | | 5/12/2006 | | |
|
|
|
|