INSP-Final Inspection | 9/28/2006 | 9/28/2006 | 9/28/2006 | P | PASS |
Forrest France
|
|
|
Corrections at fire doors are complete, fire alarm permit finaled.
|
INSP-Alarm Testing | 9/26/2006 | 9/27/2006 | 9/27/2006 | A | PART |
Forrest France
|
|
|
Remainder of fire alarm work passed inspection except one pair doors on the main level which failed to properly close upon activation of the adjacent smoke detector.
|
INSP-Sprinkler Rough-in/Hydro | 9/20/2006 | 9/26/2006 | 9/26/2006 | A | PART |
Forrest France
|
|
|
Tested notification devices for the basement, 1st floor and mezzanine levels, need to replace two strobe only with horn/strobes as the decible level is too low in one area as discussed, tested vesda systems for zones 1-4, tested two duct detectors for zone 5 and one sd for door hold open at the main level. Concluded inspection at this time due to time constraints, basement detection and new h/s to be verified at next visit.
|
INSP-Alarm Testing | 9/14/2006 | 9/21/2006 | 9/15/2006 | A | CANC |
Forrest France
|
|
|
Complete testing of all fire alarm devices within the B24C project 8790 remodel area at all levels.; Phone #: ###-#### Internet Inspection Request from: Greg Kirkes Inspection cancelled from web by: Greg Kirkes
|
INSP-Sprinkler Rough-in/Hydro | 9/8/2006 | 9/12/2006 | 9/12/2006 | A | DEFR |
Forrest France
|
|
|
Inspection request was intended for the fire sprinkler permit portion of this project, not fire alarm at this time.
|
Issue and Print Permit | | | 6/29/2006 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 5/18/2006 | | 6/23/2006 | | DONE |
Mary Froemke
|
|
|
This permit was created on the web by Paul Marcolina
|
Alarm Plan Check | | | 6/23/2006 | | PASS |
|
|
|
No written comments, pending IFC Inspector field verification.
Clarification is required on Detail 3, sheet FA4.2.
Insufficient coverage as highlighted on Sheet FA 2.1.1.
Provide information as required to Inspector at time of inspection.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/23/2006 | | DONE |
|
|
|
|
Miscellaneous action | | | 5/26/2006 | | DONE |
|
|
|
Project is large, brought back to city for review
|
Application received | | | 5/18/2006 | | DONE |
|
|
|
This permit was created on the web by Paul Marcolina
|