Permit Information
Permit NumberFIR06-00379
StatusFinaled
Name AMERICAN FIRE PROTECTION LLC
Site Address 2484 S STARLITE LN
Project NameSPR SEQUOIA HOMES INC
Customer Number 
ePlanReview 
Description
SEQUOIA HOMES INC * To install a (modified) life safety NFPA 13D system in a 4,148-ft/2 four bedroom, four bathroom, multi-level, single family dwelling. (1603-ft/2, Lower level / 2,545-ft/2, (Main level with 758-ft/2, Deck/Balcony area(s), and a 948-ft/2 attached garage/mechanical/storage). The modification is the installation of fire protection on all common walls ceilings attached to the garage and the living space. System shall be equipped with an outside alarm initiating device. All fire sprinkler work and related, which includes a dual use, single service water supply, the system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD05-02457.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/1/20099/2/20099/2/2009APASS
DetailsForrest France
Correction notice items are complete, fire sprinkler permit finaled.
INSP-Final Inspection9/1/20099/1/20099/2/2009ANR
DetailsForrest France
See correction notice for remaining items.
INSP-Final Inspection8/28/20098/31/20098/31/2009PFAIL
DetailsForrest France
Area under stairs at the lower level is missing coverage, pendent head at the riser is blocked by an adjacent soffit, riser and DCVA are three years overdue annual inspection. Outside bell tested okay, flow switch operated.
INSP-Sprinkler Rough-in8/17/20068/18/20068/21/2006PPART
DetailsForrest France
Inspection for cold cavity protection is satisfactory, OH piping is okay to cover.
INSP-Sprinkler Rough-in/Hydro7/11/20067/12/20067/13/2006PPASS
DetailsTroy Cobbley
sprinkler rough in passed.
Sprinkler Plan Check6/21/2006 7/11/2006 PASS
DetailsBill Alexander
Plan assigned to (Bill)6/21/2006 7/11/2006 DONE
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  7/11/2006 DONE
Permit Ready to Issue  7/11/2006 DONE
Telephone call  7/11/2006 DONE
Spoke with Jim and told him that permit is ready & fees///7/11/06 @ 10:27am BAS
CHANGE STATUS TO (ISS)  7/11/2006 DONE
paid fee and picked up plans
Case Summary  7/11/2006 DONE
Plan resubmittals received  6/21/2006  
Issue and Print Permit  6/14/2006 DONE
Plan assigned to (Bill)5/19/2006 5/22/2006 DONE
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  5/22/2006 DONE
Sprinkler Plan Check5/19/2006 5/22/2006 PART
DetailsBill Alexander
Re-Submittals Of The Following Items Are Required:
1. Plan is incomplete. Underground supply piping and riser shown on the plan FP1 is not identified and/or correlate with the calculations. Provide completed plans that correlates with the calculations, which shall include:
a. Underground piping shall be sized.
b. Riser piping is not identified other than size on the plans.
c. Plan FP1 has a plan not that indicates a "10'-0" rise from the street to the house," and the calculations show a 12.12 psi gain between nodes #13 (meter) and #2 (underflow of the house)?
(BMC 7-01-50-901.2, IFC 105.4.2)

2. System sprinkler head listing design is for a "flat" ceiling. This conflicts with section 1 FP-1, since the area is addressed as having a "Barrel-Vaulted Ceiling." Clarify that the slope does not exceed 2" in 12" pitch.

3. Water demand on the 1" Watts Series 007 exceeds the manufacturer's tested listing for a maximum flow rate of 7.5 ft/sec (velocity).

4. Plan (construction) information is incomplete. Water closets, showers and toilets separation is not addressed on the plan meeting the minimum allowed construction requirements by a minimum 8" lintel. If combined area exceeds 55-ft/2, fire sprinkler protection will be required. (BMC 7-01-50-901.2, IFC 105.4.2, NFPA 13D 4.1.2)

5. Backflow preventer exceeds the manufacturer's maximum system flow rate listing.

6. Water supply certificate is not addressed at the same location as this permit is addressed.

7. All unsprinklered rooms and closets shall be identified on the plans in order to verify the allowable exemption from requiring sprinkler protection.

8. Pipe friction loss shall be calculated in accordance with the Hazen-Williams formula with C values from NFPA 13-Table 14.4.4.5, which include pipe, fittings, and devices such as valves, meters, flow switches in pipes 2 in. or less in size, and strainers, and calculate elevation changes that affect the sprinkler discharge.

9. Provide corrected calculations showing the "base of riser" at node #3 and not #4, (which is the top of the riser).
Inspection Record Card- Fire5/22/2006 5/22/2006 DONE
Permit Ready to Issue  5/22/2006 DONE
Telephone call  5/22/2006 DONE
lft vm with jim dane ###-#### that permit and fees are ready to be picked up
Case Summary  5/19/2006 DONE
Application received  5/19/2006