Permit NumberFIR06-00419
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 8109 W FRANKLIN RD
Project NameCabela"s TI
Customer Number 
ePlanReview 
Description
To provide a required manual fire alarm system. The required manual fire alarm system includes sprinkler monitoring, HVAC shutdown and notification throughout. The exception for notification on water flow has been chosen and the manual pull stations are not being installed. The notification system shall be voice/evac (Cabela's standard).

The associated building permit (BLD 06-01174) is to construct interior tenant improvements for a 136,194 sq.ft. retail tenant per approved plans. Work to include, construction of interior partitions, installation of suspended ceiling systems, construction of a new mens and womens accessible restrooms, construction of a small kitchen area, miscellaneous related finishes. Deferred submittals for the mountain and aquarium fixtures. Separate permit and engineering required for any storage racking over eight feet high. Demo permit was issued under Bld06-00505 / Exterior structural permit was issued under Bld06-00632. This building is fully fire sprinklered for unlimited area provisions, any alterations or modifications to the sprinkler system shall be per NFPA #13 as regulated by the fire department. RMH RCE-6233 (CABELA'S-TENANT IMPROVEMENT)(FRANKLIN TOWN PLAZA)

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/17/20068/21/20068/21/2006APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection8/15/20068/17/20068/17/2006APART
DetailsTroy Cobbley
A temporary occupancy was given with dave hanniman's permission until the dry system for the outside canopy has been completed.
Override - Parcel Holds1/1/19001/1/19008/17/2006  
INSP-Alarm Testing8/14/20068/15/20068/15/2006ADONE
DetailsTroy Cobbley
Sound test passed today for the audio/visual devices. Four problems that need addressed are the strobe in the northeast service corridor is overspaced, the sound level in the storage room adjacent to the archery ranch is too low and both ceiling mount a/v's in the fly shop are not at the correct candella. All sprinkler items need addressed and the two horns in the fish tank/mechanical room need installed.
Override - Parcel Holds1/1/19001/1/19008/15/2006  
INSP-Alarm Testing8/14/20068/14/20068/14/2006PDONE
DetailsTroy Cobbley
Duct detector testing passed today.
Override - Parcel Holds1/1/19001/1/19008/14/2006  
Override - Parcel Holds1/1/19001/1/19008/14/2006  
INSP-Final Inspection8/11/20068/11/20068/11/2006PFAIL
DetailsTroy Cobbley
The testing today included the system smoke detectors, supervision of the NAC panels and sound levels of the notification devices. The sound levels appeared to be inadequate but per Brian the wrong scale was used. The sound levels will be reverified monday.
Override - Parcel Holds  8/11/2006  
INSP-Final Inspection8/9/20068/10/20068/10/2006PFAIL
DetailsTroy Cobbley
The only items tested and passed today are the main fire alarm panel, voice evac panel, remote fire alarm control panel in the security office and the two NAC panels. Also tested was the smoke detector in the security office.
Plan assigned to (Mary)6/5/2006 7/5/2006 DONE
Alarm Plan Check6/29/2006 7/5/2006 PASS
DetailsTroy Cobbley
Approved with comments
PLANS/APPL TAKEN TO FRONT DESK  7/5/2006 DONE
Inspection Record Card- Fire7/5/2006 7/5/2006 DONE
Telephone call  7/5/2006  
called ###-#### and left voicemail for Charlie that permit is ready and fee
Permit Ready to Issue  7/5/2006 DONE
Issue and Print Permit  7/5/2006 DONE
Plan resubmittals received  6/29/2006  
Alarm Plan Check  6/26/2006 FAIL
Resubmittal required. Faxed comments to Charlie Bayne
Plan resubmittals received  6/19/2006  
Alarm Plan Check  6/13/2006 FAIL
Resubmittal required. Faxed comments to Charlie Bayne
Application received  6/5/2006  
Case Summary  6/5/2006 DONE