Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberFIR06-00451
StatusFinaled
Name WESTERN FIRE PROTECTION INC
Site Address 2154 E SOLITUDE CT
Project NameSPR BOGATKO RESIDENCE
Customer Number 
ePlanReview 
Description
BOGATKO RESIDENCE * To install a (modified) life safety NFPA 13D system in a new 5,752-ft/2, three story single family dwelling with 2069-ft/2 first floor, 2069-ft/2 second floor, 1614-ft/2 third floor and a 907-ft/2 attached garage. The modification to this system is the installation of a single row of sidewall sprinklers along the common walls, ceilings/floor attached between the garage and any living space. System shall be equipped with an alarm initiating device and an outside alarm. All fire sprinkler work and related, which includes dual use, single service water supply, the system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD05-01473.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/23/20071/23/20071/24/2007PPASS
DetailsForrest France
Final fire sprinkler inspeciton passed, permit finaled.
INSP-Final Inspection1/22/20071/22/20071/22/2007PFAIL
DetailsForrest France
The flow switch is not powered or connected to the outside bell as required.
INSP-Sprinkler Rough-in8/3/20068/4/20068/4/2006APART
DetailsForrest France
OH fire sprinkler rough-in is good for cover.
INSP-Sprinkler Rough-in/Hydro7/30/20067/31/20067/31/2006AFAIL
DetailsForrest France
Min. spacing between sprinklers at the master bedroom is exceeded, spacing at the kitchen and pantry head may be incorrect if pantry wall is not installed as shown on plan, an accessible storage area not shown on plans below stairs will require protection, provide nailer plates where vertical risers pass through walls, still need to perform supply line flush, antifreeze sign to indicate type of solution required for CPVC.
INSP-Sprinkler Rough-in7/28/20067/28/20067/30/2006PDEFR
DetailsForrest France
###-#### colin No time available for this inspection, to be rescheduled.
Sprinkler Plan Check7/25/2006 7/27/2006 PASS
DetailsBill Alexander
Miscellaneous action  7/27/2006 DONE
Took approved revised plans to permit desk. 2nd review, no fee.
Telephone call  7/27/2006 DONE
spoke to clayton@###-####/told that permit was ready & no fee for this resubmittal
Plan resubmittals received  7/25/2006  
received by mail
Plan assigned to (Bill)6/15/2006 6/30/2006 DONE
Sprinkler Plan Check6/15/2006 6/30/2006 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  6/30/2006 DONE
Inspection Record Card- Fire6/30/2006 6/30/2006 DONE
Permit Ready to Issue  6/30/2006 DONE
Telephone call  6/30/2006 DONE
spoke to tim at ###-####/told that permit was ready-prepaid fees
CHANGE STATUS TO (ISS)  6/30/2006 DONE
already pd fee by mail
(F) Reprint permit  6/30/2006 DONE
Application received  6/15/2006