INSP-Final Inspection | 1/23/2007 | 1/23/2007 | 1/24/2007 | P | PASS |
Forrest France
|
|
|
Final fire sprinkler inspeciton passed, permit finaled.
|
INSP-Final Inspection | 1/22/2007 | 1/22/2007 | 1/22/2007 | P | FAIL |
Forrest France
|
|
|
The flow switch is not powered or connected to the outside bell as required.
|
INSP-Sprinkler Rough-in | 8/3/2006 | 8/4/2006 | 8/4/2006 | A | PART |
Forrest France
|
|
|
OH fire sprinkler rough-in is good for cover.
|
INSP-Sprinkler Rough-in/Hydro | 7/30/2006 | 7/31/2006 | 7/31/2006 | A | FAIL |
Forrest France
|
|
|
Min. spacing between sprinklers at the master bedroom is exceeded, spacing at the kitchen and pantry head may be incorrect if pantry wall is not installed as shown on plan, an accessible storage area not shown on plans below stairs will require protection, provide nailer plates where vertical risers pass through walls, still need to perform supply line flush, antifreeze sign to indicate type of solution required for CPVC.
|
INSP-Sprinkler Rough-in | 7/28/2006 | 7/28/2006 | 7/30/2006 | P | DEFR |
Forrest France
|
|
|
###-#### colin No time available for this inspection, to be rescheduled.
|
Sprinkler Plan Check | 7/25/2006 | | 7/27/2006 | | PASS |
Bill Alexander
|
|
|
|
Miscellaneous action | | | 7/27/2006 | | DONE |
|
|
|
Took approved revised plans to permit desk. 2nd review, no fee.
|
Telephone call | | | 7/27/2006 | | DONE |
|
|
|
spoke to clayton@###-####/told that permit was ready & no fee for this resubmittal
|
Plan resubmittals received | | | 7/25/2006 | | |
|
|
|
received by mail
|
Plan assigned to (Bill) | 6/15/2006 | | 6/30/2006 | | DONE |
|
|
|
|
Sprinkler Plan Check | 6/15/2006 | | 6/30/2006 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/30/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/30/2006 | | 6/30/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 6/30/2006 | | DONE |
|
|
|
|
Telephone call | | | 6/30/2006 | | DONE |
|
|
|
spoke to tim at ###-####/told that permit was ready-prepaid fees
|
CHANGE STATUS TO (ISS) | | | 6/30/2006 | | DONE |
|
|
|
already pd fee by mail
|
(F) Reprint permit | | | 6/30/2006 | | DONE |
|
|
|
|
Application received | | | 6/15/2006 | | |
|
|
|
|