Permit Number | FIR06-00460 |
Status | Finaled |
Name |
PROTEX
|
Site Address |
439 S CAPITOL BLVD
|
Project Name | BODO BLDG #8 - ALM |
Customer Number | |
ePlanReview | |
Description |
The shell/core fire alarm permit FIR05-00695 shall be finaled prior to occupancy for this space. To provide total notification in the new TI space (1st floor, 439 S. Capitol Blvd., BODO #8) and a required manual pull station at the exit. A new NAC extender panel and voice/evac panel will be installed in the generator room under this permit. No written comments. Battery calculations appear to be sufficient. Provide updated building map to the PDS Fire Inspector at time of inspection.
The associated building permit (BLD06-01093) is to construct a 1,148 square foot beverage restaurant located on the 1st story of a high-rise building. Work is to include 2 restrooms accessible to the disabled, interior nonbearing walls, suspended ceilings, an oxygen bar, millwork, and finishes. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes. The fire sprinkler system shall comply with NFPA 13 as regulated by the Fire Department. **CJW** RCE # 15898) (JUNGA JUICE - BODO BLDG #8 - 1ST STORY) This building is fire sprinklered for high-rise.
|